background image

38

39

MANIFOLDS

Manifolds are common to all systems above 30m

2

, independent of the under floor heating 

system. Manifolds are supplied complete and fixed to the wall mounting bracket.

The manifold comes complete with a drain and air vent assembly, 
which can be positioned on either end of the manifold. Isolation 
valves are supplied separately for the supply end of each manifold.
The bottom manifold is the flow and the top manifold is the 
return. Each manifold port comes complete with a Polyplumb 
push fit connection. Pipes are connected to manifolds by 
inserting a pipe stiffener into the pipe and simply push fitting 
the pipe into the port.
The flow meter on each flow port of the manifold provides 
a visual indication of the flow through each circuit.
Both manual and lockshield balancing can be undertaken 
by either using the blue cap on the return manifold for manual 
adjustment, or removing the blue cap and adjusting using the 
key supplied with each manifold. 

Preparing and installing 

the manifold

Remove the manifold from the box and arrange the flow and 
return manifolds to ensure that the inlets/outlets are pointing 
downwards. Remove the air vent and drain valve from the 
packaging and connect to the desired end of the manifold.
Ensure the seal is correctly in place before tightening the 
compression nut by hand on to the manifold. To ensure 
the valves are securely connected to the manifold, use a 
38mm spanner or wrench to tighten by a further half turn.
Remove the isolating valves (supplied separately) from the packaging 
and connect to the opposite end of the manifold. As with 
the air vent and drain valve, ensure the seal is correctly in 
place before tightening the compression nut by hand on to 
the manifold. Then, complete the connection by using a 38mm 
spanner or wrench to tighten by a further half turn. 
Fix the manifold horizontally in the desired position utilising 
both screw holes on each bracket.
The manifold is now in position and ready to be connected 
to the mains from the boiler and the under floor heating pipe 
circuits. A set of self adhesive stickers are included to help 
identify each circuit on the manifold. The stickers also provide 
the opportunity to record the number of turns required for the 
correct flow rate through each circuit (for further information 
on testing and commissioning see pages 46 and 47).

62

L

80

50

A

B

C

Outlets 

8

L (mm) 

190 

245 

300 

355 

410 

465 

520

Outlets 

10 

11 

12 

13 

14

L (mm) 

575 

630 

685 

740 

795 

850

Dimension 

1”

A (mm) 

39

B (mm) 

64

C (mm) 

86

CONNECTING TO HEAT SOURCE

Polypipe under floor heating systems are designed to be connected to a variety 

of heat source options.

Gas and oil boilers

When connecting to any heat source it is essential that the under 
floor heating manifold(s) are fed directly from the heat source with 
a dedicated set of flow and return primaries, to enable total 
independent hydraulic control of the under floor heating system. 
Under no circumstances should this primary feed be connected 
into any other heating pipework, such as radiator or domestic 
hot water primary circuits.
To provide independent hydraulic control of the entire system, it is 
important that the installation is designed as an ‘S Plan’ or ‘S Plan Plus’ 
configuration which allows for a two port zone valve to be fitted to all 
primary circuits and at each under floor heating manifold (see diagram).

IMPORTANT NOTE: 

Under no circumstances should a Polypipe 

under floor heating system be connected in to a ‘Y Plan’ (flow share) 
system as this will result in serious system operating problems.
To ensure that the correct operating temperatures and system flow 
rates are maintained for the under floor heating system, the manifold(s) 
should be fitted with a manual blending valve and circulating pump 
(see section ‘Water temperature controls’). However, it is the 
responsibility of the designer/installer to ensure that the boiler and 
system pump are capable of providing sufficient outputs in order 
to meet the requirements of the primary pipework, the under floor 
heating system and any other equipment installed in the system.

Typical ‘S Plan Plus’ configuration

 

 
 
 
Typical ‘S Plan Plus’ configuration via thermal store  

Heat pumps

Polypipe under floor heating systems are ideal for use with heat 
pump systems due to the lower operating temperatures that 
are produced by this type of heat source. However, to provide 
temperature limitation protection and sufficient system flow 
rate for the under floor heating installation, it is recommended 
to fit the manual blending valve and pump pack as supplied 
by Polypipe Building Products Ltd. 
It is the responsibility of the system design/installer to ensure that 
the heating circulation pump supplied with the heat pump, 
and any associated primary pipework, is capable of providing 
sufficient duty to meet the demand up to the under floor heating 
manifold assembly. This also applies if a ‘buffer tank’ has been 
fitted to the heat pump installation.
A buffer tank or thermal store is often fitted between the heat 
pump and the under floor heating system. This is to provide 
a sufficient quantity of stored water to feed the under floor heating 
system and to ensure that the heat pump flow rates are maintained, 
thereby reducing the risk of cycling. By using a buffer tank 
installation there is no need to use ‘open circuits’ at the under 
floor heating manifold, therefore allowing individual room control. 
 
   

 

The Underfloor Heating Manufacturers  

   

 

Association (UHMA) do not recommended  

   

 

that the under floor heating system be used  

  as an ‘open circuit’, to provide the flow rate requirement for  
  the heat pump installation, as this could lead to problems  
  with system control at a later date. For further information 
  regarding the installation of the system please contact the  
  Polypipe Technical Hotline on 

01709 770000

.

Solid fuel and wood burners

Under no circumstances should a Polypipe under floor heating 
system be connected directly to this type of heat source. 
Instead, the burner should be used to provide indirect heat via 
a thermal store or similar neutraliser. The low temperature feed 
from this store can then be pumped to the under floor heating 
manifold, as with a heat pump installation.
Please seek specialist advice from the heat source supplier 
or manufacturer before commencing the installation.

Summary of Contents for Under Floor Heating Systems

Page 1: ...s Broomhouse Lane Edlington Doncaster DN12 1ES Tel 01709 770 000 Fax 01709 770 001 2410 London Road Mount Vernon Glasgow G32 8XZ Tel 0141 778 8822 Fax 0141 778 2703 Dromore Road Lurgan Craigavon Co Ar...

Page 2: ...revious printed copies will become out of date The latest version of our installation advice including a downloadable version of the current Technical Installation Guide can be found at our trade webs...

Page 3: ...xtensive back up service Technical representation available to discuss systems in general and particular projects www ufch com Technical Installation CD Specialist Technical Hotline on 01709 770000 En...

Page 4: ...he floor screed is required by Building Regulations Edge insulation also acts as an expansion joint Floating Floor When installed in floating floors Polyplumb pipe is simply pressed in to the pre form...

Page 5: ...r requires a bespoke design You then simply input data for each room providing floor type room size and control zones to calculate the required pack All packs have a single order code and include all...

Page 6: ...h when heated will reduce to 8 9 and cause only a very small amount of shrinkage The floor will re absorb some moisture when the heating is not operating and the moisture content will increase to 12 1...

Page 7: ...d around the perimeter of the room using staples so as to prevent possible risk of the panels lifting Preparing the pipe Step 4 You will need to remove the coil from the bag leaving the shrink wrap on...

Page 8: ...ted the screed cover can be applied Care should be taken to ensure that the screed is tightly compacted around the pipe to ensure that no voids are present The system should remain under pressure 6 ba...

Page 9: ...nder pressure whilst the flooring is laid Finishing The room can then be finished by fitting 18mm or 22mm tongue and groove sheets of chipboard glued on the edge over the floating floor system Mark th...

Page 10: ...hed downwards and away from the underside of the timber finished floor covering as this could lead to potential underperformance of the system Testing Step 4 Once the pipe circuits have been installed...

Page 11: ...These can be fixed directly through the spreader plate down in to the joists below It is important to indicate the position of pipework in areas where the additional fixing of items such as carpet gri...

Page 12: ...heir high output at relatively low flow temperatures Modular Heating Panels are ideal for maximising heat efficiency and lowering energy consumption In most installations it is not necessary to cover...

Page 13: ...should be selected The span is defined as the free space from wall to wall that needs to remain uninterrupted by trimmers or other services Ideally install MHP panels prior to other services whenever...

Page 14: ...omes into direct contact with it Always ensure that electrical cables are not in physical contact with the MHP panels using tape or a polythene strip Finishing Once you have connected your system up t...

Page 15: ...for heavyweight floor coverings such as ceramics or where the floor covering needs to be secured directly to the panel e g solid wood Overlay Lite is a high compressive strength lightweight insulated...

Page 16: ...is should be the first consideration for most projects The more structural nature of Overlay however makes it ideal for direct tiling or application of floor finishes which need to be fixed or screwed...

Page 17: ...mple of blanking in a bathroom Example of squaring off an irregular room plan Room layouts The following diagrams show some examples of room shapes pipe requirements and interruptions pillars hearths...

Page 18: ...wood floors they can be discretely screwed through the tongue and groove directly into the Overlay panel avoiding pipe circuitry to minimise movement in the floor covering If over boarding with 6mm p...

Page 19: ...r covering as normal It is advisable to mark out pipe positioning to avoid stapling pipes when fitting carpets 36 37 Overlay Lite for lightweight floor coverings Installation Laying end returns Step 1...

Page 20: ...stic hot water primary circuits To provide independent hydraulic control of the entire system it is important that the installation is designed as an S Plan or S Plan Plus configuration which allows f...

Page 21: ...d in under floor heating systems is less than that required for radiators or stored hot water If these other services are connected to the same boiler it will be necessary to control the water tempera...

Page 22: ...iring centre and slave units Available in two surface finishes and offers the following features Large touch screen display with high visibility blue LED backlight On screen display shows current stat...

Page 23: ...distribution pipe work Connection from nearest radiator 260mm 200mm Pump Pipe thermostat Heating return Heating flow Under floor heating flow Under floor heating return Thermostatic blending valve Pu...

Page 24: ...ible tap connectors for the simplest method of connection Close all under floor heating circuits except one by screwing down the blue caps and closing the isolating valves situated on top of the manif...

Page 25: ...resistant to the build up of scale Short term chlorination for disinfection of supply pipe work and normal levels of chlorine in UK domestic water supplies will not have an adverse effect on the integ...

Page 26: ...ng should be done with all switches on and room thermostats calling Fault finding complete Adjust pump speed and set flow rates in accordance with the system design data as provided NO NO Is the boile...

Page 27: ...Manufacturing quality assurance In accordance with BS ES ISO 9001 2000 BSI registered firm Certificate FM00318 Installation standard To follow the recommendations of BS5955 Part 8 2001 Plastic Pipewo...

Page 28: ...OR HEATING REQUIREMENTS Manifold Position s Please also indicate on drawing Floor Type Solid Suspended Floating MHP Overlay Overlay Lite Ground Floor 1st Floor 2nd Floor CONSTRUCTION DETAILS If NOT to...

Reviews: