background image

40

41

ROOM TEMPERATURE CONTROL

Controlling under floor heating

The control of under floor heating systems is different to that 
of conventional radiator systems, as the space should not 
be allowed to cool completely during the heating season. 
The temperature during unoccupied or night time periods 
should fall to around 4°C lower than the occupied temperature.
This lower temperature setting is known as the set-back 
temperature, e.g. occupied temperature 21°C, set-back 
temperature 17°C. 

Individual room control

Polypipe under floor heating controls allow each room to 
be both time and temperature controlled via the use of a 
programmable room thermostat. Each thermostat is wired 
back to a master wiring centre and slave unit, which in turns 
operates the relevant manifold actuator/s, the under floor 
heating pump, and the two-port zone valve. The master wiring 
centre is also capable of providing either a 230V or a Volt free 
switched live supply to signal the boiler.

Schematic switching diagram - relays not shown

 

 
As individual rooms reach their set point temperature or when 
the system is operating in ‘set back’ mode the master wiring 
centre will de-energise the pump and zone valve and the signal 
to the boiler will be cut, ensuring that maximum comfort levels 
and system efficiencies are achieved and maintained at all times.

The number of control zones you require will depend on the 
number of rooms you wish to control individually. The 4, 6 and 
8 zone packs describe the number of areas you wish to control, 
not necessarily the number of circuits you are supplying from 
that manifold. To optimise the use of each control pack you will 
need to understand the following guidelines:
•   The 4 zone pack contains 4 room thermostats; the 6 zone 

pack contains 6 room thermostats; and the 8 zone pack 
contains 8 room thermostats

•   Each room thermostat can control 1 zone and 

up to 4 actuators

•   Rooms over 40m

2

 should be allocated as 2 zones 

and have 2 room thermostats

•  An actuator is required on each circuit that requires control

The room thermostats (PBPRP) and wiring centres are available 
as individual items or packs, as detailed below:

A comprehensive range of room temperature control products are available 

to complement Polypipe under floor heating systems. Designed specifically to 

maximise both comfort and efficiency, the unique programming functions provide 

the perfect control solution for under floor heating systems.

WATER TEMPERATURE CONTROLS

The temperature of water required in under floor heating systems is less than 

that required for radiators or stored hot water. If these other services are 

connected to the same boiler it will be necessary to control the water 

temperature using one of the Polypipe water temperature control units.

All Polypipe under floor heating system packs supplied through 
the                 selection process will contain all the appropriate 
control products.

 

 

Modulating pump unit 

(PB970014)

The modulating pump unit controls water temperatures between 
45°C and 60°C. The inclusion of a modulating pump ensures 
that the flow to the under floor heating circuits is automatically 
adjusted to allow for the opening and closing of actuators 
when individual room temperature is required. The unit is 
suitable for manifolds demanding up to 15kW heat load.
The temperature of the water is set using the pilot pin on the 
hand wheel. When the pilot pin is flush with the hand wheel 
the temperature is set to 55°C. Each click to + or – increases 
or decreases the temperature by 1°C.
The modulating pump unit is fitted directly to the manifold at 
either end by turning the pump through 180°. An additional 
zone valve is required when using a modulating pump unit 
supplied by other manufacturers. 

Floor heating control pack 

(PB970015)

The pack controls water temperatures between 35°C and 60°C, 
and incorporates a fixed head pump and a 22mm 2-port zone 
valve, which is suitable for manifolds demanding up to 15kW heat 
load. The set temperature of the water is shown on the wheel head. 
The control pack is fitted directly to the manifold at either end, 
as both left hand and right hand connector bends are supplied 
with the unit. 

Dimensions of assembled unit

 
 
 
 

 

NOTE:

 The valves shown on this diagram are purchased 

separately and not supplied with the unit. 

Manifold bends (PB12735)

The water temperature control packs can be fitted at 90° to 
the manifold using the manifold bends. This allows manifolds 
and pump units to be corner mounted where space is at a 
premium, e.g. in an understairs cupboard.

A)

 Manifold bend installed with modulating pump unit

B)

 Manifold bend installed with floor heating control pack

A)

B)

290mm

Pilot pin flush 

to handwheel

260mm

155mm

110mm

50mm

30mm

130mm

40mm

Product 

Class Rating  IP Rating

PBPRP 

Class 2 

IP30

PBPRP RF 

Class 2 

IP30

PBTSP 

Class 2 

IP20

Electrical protection index

Actuator

room 2

closed

Actuator

room 1

open

Room 

thermostat 

room 2

satisfied

Room 

thermostat 

room 1 

demand

Zone 

valve open

Circuit 

room 1 open

Circuit 

room 2 closed

Boiler

on

UFH Pump

on

Pack 

Single Zone  4 Zone 

6 Zone 

8 Zone

 

PB1ZP 

PB4ZP 

PB6ZP 

PB8ZP

1 Zone Master 

1

4 Zone Slave 

 

 

2

6 Zone Slave 

 

 

Programmable 
Room Thermostat 

8

Pack

Code

Content

Summary of Contents for Under Floor Heating Systems

Page 1: ...s Broomhouse Lane Edlington Doncaster DN12 1ES Tel 01709 770 000 Fax 01709 770 001 2410 London Road Mount Vernon Glasgow G32 8XZ Tel 0141 778 8822 Fax 0141 778 2703 Dromore Road Lurgan Craigavon Co Ar...

Page 2: ...revious printed copies will become out of date The latest version of our installation advice including a downloadable version of the current Technical Installation Guide can be found at our trade webs...

Page 3: ...xtensive back up service Technical representation available to discuss systems in general and particular projects www ufch com Technical Installation CD Specialist Technical Hotline on 01709 770000 En...

Page 4: ...he floor screed is required by Building Regulations Edge insulation also acts as an expansion joint Floating Floor When installed in floating floors Polyplumb pipe is simply pressed in to the pre form...

Page 5: ...r requires a bespoke design You then simply input data for each room providing floor type room size and control zones to calculate the required pack All packs have a single order code and include all...

Page 6: ...h when heated will reduce to 8 9 and cause only a very small amount of shrinkage The floor will re absorb some moisture when the heating is not operating and the moisture content will increase to 12 1...

Page 7: ...d around the perimeter of the room using staples so as to prevent possible risk of the panels lifting Preparing the pipe Step 4 You will need to remove the coil from the bag leaving the shrink wrap on...

Page 8: ...ted the screed cover can be applied Care should be taken to ensure that the screed is tightly compacted around the pipe to ensure that no voids are present The system should remain under pressure 6 ba...

Page 9: ...nder pressure whilst the flooring is laid Finishing The room can then be finished by fitting 18mm or 22mm tongue and groove sheets of chipboard glued on the edge over the floating floor system Mark th...

Page 10: ...hed downwards and away from the underside of the timber finished floor covering as this could lead to potential underperformance of the system Testing Step 4 Once the pipe circuits have been installed...

Page 11: ...These can be fixed directly through the spreader plate down in to the joists below It is important to indicate the position of pipework in areas where the additional fixing of items such as carpet gri...

Page 12: ...heir high output at relatively low flow temperatures Modular Heating Panels are ideal for maximising heat efficiency and lowering energy consumption In most installations it is not necessary to cover...

Page 13: ...should be selected The span is defined as the free space from wall to wall that needs to remain uninterrupted by trimmers or other services Ideally install MHP panels prior to other services whenever...

Page 14: ...omes into direct contact with it Always ensure that electrical cables are not in physical contact with the MHP panels using tape or a polythene strip Finishing Once you have connected your system up t...

Page 15: ...for heavyweight floor coverings such as ceramics or where the floor covering needs to be secured directly to the panel e g solid wood Overlay Lite is a high compressive strength lightweight insulated...

Page 16: ...is should be the first consideration for most projects The more structural nature of Overlay however makes it ideal for direct tiling or application of floor finishes which need to be fixed or screwed...

Page 17: ...mple of blanking in a bathroom Example of squaring off an irregular room plan Room layouts The following diagrams show some examples of room shapes pipe requirements and interruptions pillars hearths...

Page 18: ...wood floors they can be discretely screwed through the tongue and groove directly into the Overlay panel avoiding pipe circuitry to minimise movement in the floor covering If over boarding with 6mm p...

Page 19: ...r covering as normal It is advisable to mark out pipe positioning to avoid stapling pipes when fitting carpets 36 37 Overlay Lite for lightweight floor coverings Installation Laying end returns Step 1...

Page 20: ...stic hot water primary circuits To provide independent hydraulic control of the entire system it is important that the installation is designed as an S Plan or S Plan Plus configuration which allows f...

Page 21: ...d in under floor heating systems is less than that required for radiators or stored hot water If these other services are connected to the same boiler it will be necessary to control the water tempera...

Page 22: ...iring centre and slave units Available in two surface finishes and offers the following features Large touch screen display with high visibility blue LED backlight On screen display shows current stat...

Page 23: ...distribution pipe work Connection from nearest radiator 260mm 200mm Pump Pipe thermostat Heating return Heating flow Under floor heating flow Under floor heating return Thermostatic blending valve Pu...

Page 24: ...ible tap connectors for the simplest method of connection Close all under floor heating circuits except one by screwing down the blue caps and closing the isolating valves situated on top of the manif...

Page 25: ...resistant to the build up of scale Short term chlorination for disinfection of supply pipe work and normal levels of chlorine in UK domestic water supplies will not have an adverse effect on the integ...

Page 26: ...ng should be done with all switches on and room thermostats calling Fault finding complete Adjust pump speed and set flow rates in accordance with the system design data as provided NO NO Is the boile...

Page 27: ...Manufacturing quality assurance In accordance with BS ES ISO 9001 2000 BSI registered firm Certificate FM00318 Installation standard To follow the recommendations of BS5955 Part 8 2001 Plastic Pipewo...

Page 28: ...OR HEATING REQUIREMENTS Manifold Position s Please also indicate on drawing Floor Type Solid Suspended Floating MHP Overlay Overlay Lite Ground Floor 1st Floor 2nd Floor CONSTRUCTION DETAILS If NOT to...

Reviews: