40
41
ROOM TEMPERATURE CONTROL
Controlling under floor heating
The control of under floor heating systems is different to that
of conventional radiator systems, as the space should not
be allowed to cool completely during the heating season.
The temperature during unoccupied or night time periods
should fall to around 4°C lower than the occupied temperature.
This lower temperature setting is known as the set-back
temperature, e.g. occupied temperature 21°C, set-back
temperature 17°C.
Individual room control
Polypipe under floor heating controls allow each room to
be both time and temperature controlled via the use of a
programmable room thermostat. Each thermostat is wired
back to a master wiring centre and slave unit, which in turns
operates the relevant manifold actuator/s, the under floor
heating pump, and the two-port zone valve. The master wiring
centre is also capable of providing either a 230V or a Volt free
switched live supply to signal the boiler.
Schematic switching diagram - relays not shown
As individual rooms reach their set point temperature or when
the system is operating in ‘set back’ mode the master wiring
centre will de-energise the pump and zone valve and the signal
to the boiler will be cut, ensuring that maximum comfort levels
and system efficiencies are achieved and maintained at all times.
The number of control zones you require will depend on the
number of rooms you wish to control individually. The 4, 6 and
8 zone packs describe the number of areas you wish to control,
not necessarily the number of circuits you are supplying from
that manifold. To optimise the use of each control pack you will
need to understand the following guidelines:
• The 4 zone pack contains 4 room thermostats; the 6 zone
pack contains 6 room thermostats; and the 8 zone pack
contains 8 room thermostats
• Each room thermostat can control 1 zone and
up to 4 actuators
• Rooms over 40m
2
should be allocated as 2 zones
and have 2 room thermostats
• An actuator is required on each circuit that requires control
The room thermostats (PBPRP) and wiring centres are available
as individual items or packs, as detailed below:
A comprehensive range of room temperature control products are available
to complement Polypipe under floor heating systems. Designed specifically to
maximise both comfort and efficiency, the unique programming functions provide
the perfect control solution for under floor heating systems.
WATER TEMPERATURE CONTROLS
The temperature of water required in under floor heating systems is less than
that required for radiators or stored hot water. If these other services are
connected to the same boiler it will be necessary to control the water
temperature using one of the Polypipe water temperature control units.
All Polypipe under floor heating system packs supplied through
the selection process will contain all the appropriate
control products.
Modulating pump unit
(PB970014)
The modulating pump unit controls water temperatures between
45°C and 60°C. The inclusion of a modulating pump ensures
that the flow to the under floor heating circuits is automatically
adjusted to allow for the opening and closing of actuators
when individual room temperature is required. The unit is
suitable for manifolds demanding up to 15kW heat load.
The temperature of the water is set using the pilot pin on the
hand wheel. When the pilot pin is flush with the hand wheel
the temperature is set to 55°C. Each click to + or – increases
or decreases the temperature by 1°C.
The modulating pump unit is fitted directly to the manifold at
either end by turning the pump through 180°. An additional
zone valve is required when using a modulating pump unit
supplied by other manufacturers.
Floor heating control pack
(PB970015)
The pack controls water temperatures between 35°C and 60°C,
and incorporates a fixed head pump and a 22mm 2-port zone
valve, which is suitable for manifolds demanding up to 15kW heat
load. The set temperature of the water is shown on the wheel head.
The control pack is fitted directly to the manifold at either end,
as both left hand and right hand connector bends are supplied
with the unit.
Dimensions of assembled unit
NOTE:
The valves shown on this diagram are purchased
separately and not supplied with the unit.
Manifold bends (PB12735)
The water temperature control packs can be fitted at 90° to
the manifold using the manifold bends. This allows manifolds
and pump units to be corner mounted where space is at a
premium, e.g. in an understairs cupboard.
A)
Manifold bend installed with modulating pump unit
B)
Manifold bend installed with floor heating control pack
A)
B)
290mm
Pilot pin flush
to handwheel
260mm
155mm
110mm
50mm
30mm
130mm
40mm
Product
Class Rating IP Rating
PBPRP
Class 2
IP30
PBPRP RF
Class 2
IP30
PBTSP
Class 2
IP20
Electrical protection index
Actuator
room 2
closed
Actuator
room 1
open
Room
thermostat
room 2
satisfied
Room
thermostat
room 1
demand
Zone
valve open
Circuit
room 1 open
Circuit
room 2 closed
Boiler
on
UFH Pump
on
Pack
Single Zone 4 Zone
6 Zone
8 Zone
PB1ZP
PB4ZP
PB6ZP
PB8ZP
1 Zone Master
1
1
1
1
4 Zone Slave
1
2
6 Zone Slave
1
Programmable
Room Thermostat
1
4
6
8
Pack
Code
Content