background image

 

2.6 

Filling the Reservoir  

The maximum fill level for the Circulating bath is one inch 

(25mm) below the top of the reservoir. A liquid level that fully 

covers the heater coil, pump, over-temperature sensor, and at 

least one inch (25mm) of the temperature sensor must be 

maintained. For optimum cooling efficiency, the bath fluid level in 

Refrigerating/Heating Circulators should be kept above the 
cooling coils at all times. 

Upon start-up, it may be necessary to add fluid to compensate 

for the fluid required for external circulation. If the proper fluid 

level is not maintained, the heater coil may become exposed and possibly damaged. 

2.7 

Reservoir Purge 

When operating at low temperatures, atmospheric moisture tends to migrate into the reservoir and 

condense. The 1/8 inch OD Reservoir Purge tube allows you to inject inert gas into the Circulating 

bath to prevent the build-up of condensation. 

 

Section 3- Immersion Circulator   

3.1 

Contents  

 

 

—  Immersion Circulator 

 

 

—  Operators Manual 

 

 

—  Warranty Card 

 

 

—  IEC Power Cord 

3.2 

General Description  

Immersion Circulators with Standard Controller are designed for use in user-supplied reservoirs. 

These units can be used with many sizes and shapes of reservoirs, making them extremely versatile 

and useful for a wide variety of applications. 

    

Model Type 

Temperature  

Range 

Reservoir  

Capacity 

Amps @  

120V, 60Hz 

Amps @  

240V, 50Hz 

Heat Only  

Immersion Circulator 

5°C to 150°C* 

N/A 

11A 

7.5A 

3.3 

Circulator Pump 

The HIGH or LOW speed selection switch on the rear panel of the Controller is used to select pump 

speed. LOW is adequate for most applications and provides quieter pumping. HIGH is 

recommended where temperature varies frequently and there is a need for fast recovery or when 

pumping to multiple external units. 

Speed 

Maximum Pump Outlet Ratings  

Selection  

Line Frequency = 50/60Hz 

 

HIGH 

15 LPM / 2.6 PSI 

 

LOW 

9 LPM / 1.5 PSI 

 

The data in the table above are based on the following criteria: 

1.  Maximum pump outlet flow rate is measured in liters per minute (LPM) with no restriction on the pump outlet. 
2.  Maximum pump outlet pressure is measured in pounds per square inch (PSI) at no flow. 
3.  Water was used as the circulation fluid. Water has a viscosity of one centistoke. High viscosity or low-density 

fluids will change these figures. 

 

Warning

: These units are equipped with over-temperature protection (Safety Set).  A low-liquid 

level or failure to set the Safety Set and properly immerse the heater may result in heater 

burnout and triac failure. While operating, do not allow the heater to contact any potentially 

flammable materials, such as plastic racks or sides of plastic tanks, as a fire hazard may result. 

Minimum 

fill level 

Temperature 

Sensor 

Summary of Contents for Standard Controller

Page 1: ...Operators Manual Standard Controller Models Pages 1 22 Manuel de l utilisateur Mod les du Contr leur Standard Pages 21 37 Bedienungsanleitung Ger te mit Standardregelung Seiten 38 54 110 227 1 8 08...

Page 2: ...D 1150S 1157P 1196D 1190S 1197P 1186D 1180S 1187P 1136D 1130S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 121...

Page 3: ...rces prudently and rationally Specific treatment of WEEE is indispensable in order to avoid the dispersion of pollutants into the recycled material or waste stream Such treatment is the most effective...

Page 4: ...130S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 12100 15 12100 20 12100 25 12108 00 12108 05 12108 20 12108...

Page 5: ...0S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 12100 15 12100 20 12100 25 12108 00 12108 05 12108 20 12108 25...

Page 6: ...tting the Safety Set Set Point 5 5 Selecting Temperature Units 5 6 Setting the Software High Limit 5 7 Setting the Set point Temperature 5 8 User Defined Preset Temperatures 5 9 Local Lockout Feature...

Page 7: ...is warranty is limited to the repair or replacement of a defective product and shall not in any event be liable for any incidental or consequential damages of any kind resulting from use or possession...

Page 8: ...ration at temperatures below 40 C However refrigeration should not be used when the fluid temperature is above 55 C Refrigeration should not be turned on when the ambient air temperature is above 32 C...

Page 9: ...h the unit are intended for applications from 40 C to 93 C For applications above 93 C brass stainless steel or Teflon fittings are recommended inch NPT to M16 stainless steel male adapter fittings ar...

Page 10: ...for a wide variety of applications Model Type Temperature Range Reservoir Capacity Amps 120V 60Hz Amps 240V 50Hz Heat Only Immersion Circulator Ambient 5 C to 150 C N A 11A 7 5A 3 3 Circulator Pump Th...

Page 11: ...ing over the rotating pump outlet nozzle and fasten it in place with a hose clamp Connect the other end of the tubing to the inlet of the external apparatus Be sure to run tubing from the outlet of th...

Page 12: ...eset Button 13 Pump Inlet 2 4 Safety Set Indicator Knob 14 Reservoir Purge 2 5 Cooling Light 1 15 Pump Outlet 2 6 Power ON OFF Button 16 AC Input 7 Heating Light 17 Circuit Breaker AC Power Switch 8 F...

Page 13: ...the Circulator on a level surface free from drafts and out of direct sunlight Do not place it where there are corrosive fumes excessive moisture high room temperatures or excessive dust is present Re...

Page 14: ...After filling the reservoir with fluid you must set the Safety Set and the Software High Limit as well as your desired control set point temperature 5 4 Setting the Safety Set Set Point The Safety Set...

Page 15: ...the problem is corrected bath temperature reduced or Software High Limit value increased press the Power button to clear the message 5 7 Setting the Set Point Temperature Press and release the Select...

Page 16: ...ons a set point 15 C above room temperature is recommended Cool Command Refrigeration Refrigerating Heating Circulators with 13 and 28 liter reservoirs feature the advanced Cool Command modulating ref...

Page 17: ...FLt 5 Probe failure Error Service required FLt 6 i2c error Communication failure to modulation board Error Service required Appears only on Refrigerating Heating Circulators Section 6 Calibration and...

Page 18: ...ing capacity the condenser the front and back air vents and reusable filter should be kept free of dust and dirt They should be checked on a scheduled basis and cleaned as required The reusable filter...

Page 19: ...o stabilize when changes in heat load or set point are made 7 6 No Cooling or Insufficient Cooling Check that the Cooling switch is ON If the cooling light is not lit check the control temperature set...

Page 20: ...RMAL EXTREME 25 C RANGE RANGE Distilled Water 1 00 10 90 C 2 100 C Ethylene Glycol 30 Water 70 90 0 95 C 15 107 C Ethylene Glycol 50 Water 50 82 20 100 C 30 100 C Dynalene HC 50 76 50 60 C 62 60 C DC2...

Page 21: ...s high temperature extreme 1 Heat loss from vapor adversely affects temperature stability 2 To prevent the accumulation of vapors inside the room the reservoir may need to be placed in a fume hood 3...

Page 22: ...Refrigerating Heating and Heating Only models 120V 525 525 Pump Motor Refrigerating Heating and Heating Only models 240V 525 526 Pump Motor Immersion Circulators 120V 525 527 Pump Motor Immersion Cir...

Reviews: