background image

 

2.3    

Circulator Pump  

The two-speed simplex (pressure) pump may be used for tempering of samples 

in the reservoir or for circulation in closed loops. It is not designed for pumping 

from the circulator's reservoir into and out of a second open reservoir.   

The HIGH or LOW Speed Selection Switch on the rear of the Controller is used to 

select pump speed. LOW is adequate for most applications and provides quieter 

pumping. HIGH is recommended where temperature varies frequently and there 
is a need for fast recovery or when pumping to multiple external units.    

Speed 

Maximum Pump Outlet Ratings 

Selection  

Line Frequency = 50/60Hz 

 

HIGH 

15 LPM / 2.6 PSI 

 

LOW 

9 LPM / 1.5 PSI 

 

The data in the table above are based on the following criteria: 

1.  Maximum pump outlet flow rate is measured in liters per minute (LPM) with no restriction on the pump outlet. 
2.  Maximum pump outlet pressure is measured in pounds per square inch (PSI) at no flow. 
3. 

Water was used as the circulation fluid.  Water has a viscosity of one centistoke.  High viscosity or low-
density fluids will change these figures. 

 

2.4 

Pump Inlet and Outlet Connections  

The pump inlet and outlet ports are female ¼ inch NPT connections that 

permit use of barbed tubing adapters or hard plumbing fittings. ½ inch 

(13mm) ID tubing may also be slid over these connections and held in place 

with a hose clamp. If the pump inlet and outlet are not used for external 

circulation, they should be connected using the Buna N Bypass Hose 
provided with the unit in order to optimize fluid mixing within the reservoir. 

The nylon barbed tubing adapter fittings supplied with the unit are intended 

for applications from -40°C to 93°C.  For applications above 93°C, brass, stainless steel, or Teflon

®

 

fittings are recommended. ¼ inch NPT to M16 stainless steel male adapter fittings are provided with 

all 50Hz models. 

It is the user’s responsibility to ensure that the tubing and fittings connected to the Circulator are 

compatible with the bath fluid and temperature range being used.  

NOTE: The use of quick-connect fittings is not recommended as they typically restrict flow rate. 

2.5  

Closed Loop Circulation 

Connect the pump inlet and outlet to the external apparatus. To maintain adequate flow, avoid 
restrictions in the tubing. When connecting the Circulator to more than two closed loops, the use of a 

manifold made of "Y" adapters to divide the fluid into multiple banks is recommended. After setting 

up multiple closed loops, check for adequate flow at the return manifold of each loop and check that 

the bath fluid is at an adequate level. A booster pump may be added to closed loops without 

damaging the Circulator’s bath pump.  

The temperature control stability of a closed loop system is better at the external apparatus than in 

the Circulator reservoir (provided the control point of the apparatus represents a constant load and is 

well insulated). For example, if you circulate fluid through a viscometer at 50°C, the temperature 
variation observed in the Circulator reservoir may be ±0.2°C while the temperature variation in the 

viscometer may be only ±0.1°C.  

Although temperature stability is generally better at the external apparatus control point, depending 

on the length of tubing used and the efficiency of the insulation, the actual temperature reading at 

the external apparatus may be slightly different than the temperature reading at the Circulator 

reservoir. 

Summary of Contents for Standard Controller

Page 1: ...Operators Manual Standard Controller Models Pages 1 22 Manuel de l utilisateur Mod les du Contr leur Standard Pages 21 37 Bedienungsanleitung Ger te mit Standardregelung Seiten 38 54 110 227 1 8 08...

Page 2: ...D 1150S 1157P 1196D 1190S 1197P 1186D 1180S 1187P 1136D 1130S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 121...

Page 3: ...rces prudently and rationally Specific treatment of WEEE is indispensable in order to avoid the dispersion of pollutants into the recycled material or waste stream Such treatment is the most effective...

Page 4: ...130S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 12100 15 12100 20 12100 25 12108 00 12108 05 12108 20 12108...

Page 5: ...0S 1137P 1136 1D 1130 1S 1137 1P 1136 2D 1130 2S 1137 2P 12110 00 12110 05 12112 01 12112 06 12112 11 12112 16 12112 12 12112 26 12100 10 12100 15 12100 20 12100 25 12108 00 12108 05 12108 20 12108 25...

Page 6: ...tting the Safety Set Set Point 5 5 Selecting Temperature Units 5 6 Setting the Software High Limit 5 7 Setting the Set point Temperature 5 8 User Defined Preset Temperatures 5 9 Local Lockout Feature...

Page 7: ...is warranty is limited to the repair or replacement of a defective product and shall not in any event be liable for any incidental or consequential damages of any kind resulting from use or possession...

Page 8: ...ration at temperatures below 40 C However refrigeration should not be used when the fluid temperature is above 55 C Refrigeration should not be turned on when the ambient air temperature is above 32 C...

Page 9: ...h the unit are intended for applications from 40 C to 93 C For applications above 93 C brass stainless steel or Teflon fittings are recommended inch NPT to M16 stainless steel male adapter fittings ar...

Page 10: ...for a wide variety of applications Model Type Temperature Range Reservoir Capacity Amps 120V 60Hz Amps 240V 50Hz Heat Only Immersion Circulator Ambient 5 C to 150 C N A 11A 7 5A 3 3 Circulator Pump Th...

Page 11: ...ing over the rotating pump outlet nozzle and fasten it in place with a hose clamp Connect the other end of the tubing to the inlet of the external apparatus Be sure to run tubing from the outlet of th...

Page 12: ...eset Button 13 Pump Inlet 2 4 Safety Set Indicator Knob 14 Reservoir Purge 2 5 Cooling Light 1 15 Pump Outlet 2 6 Power ON OFF Button 16 AC Input 7 Heating Light 17 Circuit Breaker AC Power Switch 8 F...

Page 13: ...the Circulator on a level surface free from drafts and out of direct sunlight Do not place it where there are corrosive fumes excessive moisture high room temperatures or excessive dust is present Re...

Page 14: ...After filling the reservoir with fluid you must set the Safety Set and the Software High Limit as well as your desired control set point temperature 5 4 Setting the Safety Set Set Point The Safety Set...

Page 15: ...the problem is corrected bath temperature reduced or Software High Limit value increased press the Power button to clear the message 5 7 Setting the Set Point Temperature Press and release the Select...

Page 16: ...ons a set point 15 C above room temperature is recommended Cool Command Refrigeration Refrigerating Heating Circulators with 13 and 28 liter reservoirs feature the advanced Cool Command modulating ref...

Page 17: ...FLt 5 Probe failure Error Service required FLt 6 i2c error Communication failure to modulation board Error Service required Appears only on Refrigerating Heating Circulators Section 6 Calibration and...

Page 18: ...ing capacity the condenser the front and back air vents and reusable filter should be kept free of dust and dirt They should be checked on a scheduled basis and cleaned as required The reusable filter...

Page 19: ...o stabilize when changes in heat load or set point are made 7 6 No Cooling or Insufficient Cooling Check that the Cooling switch is ON If the cooling light is not lit check the control temperature set...

Page 20: ...RMAL EXTREME 25 C RANGE RANGE Distilled Water 1 00 10 90 C 2 100 C Ethylene Glycol 30 Water 70 90 0 95 C 15 107 C Ethylene Glycol 50 Water 50 82 20 100 C 30 100 C Dynalene HC 50 76 50 60 C 62 60 C DC2...

Page 21: ...s high temperature extreme 1 Heat loss from vapor adversely affects temperature stability 2 To prevent the accumulation of vapors inside the room the reservoir may need to be placed in a fume hood 3...

Page 22: ...Refrigerating Heating and Heating Only models 120V 525 525 Pump Motor Refrigerating Heating and Heating Only models 240V 525 526 Pump Motor Immersion Circulators 120V 525 527 Pump Motor Immersion Cir...

Reviews: