26
Figure 5.5.5: Remote Connection for Honda EM7000iS, EU6500iS,
EM6500SXK1/K2, EM5000SXK2/K3, EM5000iS, EM4000SX&EM3800SX
(2) Refer to the table below for minimum copper wire sizing and ratings.
Table 5.5.2: Minimum Copper Wire Sizing and Ratings
AC
Solar
Enternet
Voltage Rating
600V
1000V
30V
Temp. Class
75°C
75°C
60°C
Gauge
5K
6AWG
12AWG
Standard Ethernet cable
7K
10AWG
12AWG
Standard Ethernet cable
6. Basic Operations
6.1 Boot System
(1) Switch on the
POWER
switch on the BCMS module,
wait 60 seconds
until
the BCMS and Battery Module start normally
, and
(2) Switch on the
PV SWITCH
on the Solar Controller, and
(3) Switch on the
MAIN
switch on PCS module
.
WARNING:
Failure to follow the instructions may damage the device.
6.2 Shut Down System
(1) Switch off the
MAIN
switch on PCS module, and
(2) Switch off the
PV SWITCH
on the Solar Controller, and
(3) Switch off the
POWER
switch on the BCMS module
.