Automatic boiler for wood pellets
38
8.2
OPERATING CONDITIONS – MAIN MENU
SELECTION OF OPERATING MODE
User - before start operation of boiler, have to select operation mode – touch on the button is
automatically changed mode:
FIXED POWER
Operate boiler automatically on the fixed power. User can set value of power (% or kW) and temperature (°C).
MODULATION
Operate boiler automatically. User can set value temperature (°C). The power is adjusted automatically depend on
temperature. User cannot change the power.
EQUITHERM
Operate boiler automatically. The power and temperature is adjusted automatically depend on outside temperature and
setting of equitherm
diagram. User cannot change the power and temperature.
This mode user cannot chose when the out temperature sensor is not use.
Selection – touch on button:
FIXED POWER
»
MODULATION
»
EQUITHERM
START
After touch on the button START boiler is working automatically. The display shows step by step actual
operation:
Ignition
Fuel is burn on by electric spiral.
Stabilisation
Stabilisation of fire
Operating
The fire was stabilised and boiler is normally working.
Stand-by
Quiet mode of the boiler, when the boiler is not burning actively. Boiler is ready on the basis of impulse from surrounding
equipment (thermostats, GSM Modem) to restore the supply of heat.
Note:
Change –SELECTION OF OPERATING MODE – is possible to make at any time during operation.
Note:
If boiler is working
in -MODULATION or EQUITHERM - control unit automatically setting power in the range 0
– 10.
Note:
After „START“ is activated automatic ignition. Auto ignition runs for several minutes.
The programme routine of Automatic Ignition has absolute priority to be carried out in full extent. If the routine is
activated, it is not possible to interrupt or stop it in any way. This fact is an important condition for reliable operation of
the boiler because it is then possible only to ascertain indirectly from further behaviour of the boiler whether it is burning
or not.
The on-going routine of Automatic Ignition may be terminated only by the operator by switching
STOP
.
Service is than
responsible for the correct set up to a automatic operation
.
Note:
If the boiler is working in the mode
FIXED POWER, MODULATION, EQUITHERM
and power supply is
interrupted the boiler will start with the electric ignition routine after the power supply is resumed.
Summary of Contents for KP 12S
Page 1: ......
Page 17: ...Automatic boiler for wood pellets 16 Picture No 9 Feeder F1 4 5 1 4 5 2 4 5 3 4 5 4 4 5 5 ...
Page 28: ...Automatic boiler for wood pellets 27 Picture No 20 Ceramic grate parts placement guide ...
Page 41: ...Automatic boiler for wood pellets 40 8 3 1 2 Menu users settings ...
Page 43: ...Automatic boiler for wood pellets 42 Cleaning an ash removing Skin Time window setting ...
Page 46: ...Automatic boiler for wood pellets 45 Actual values Configuration ...
Page 52: ...Automatic boiler for wood pellets 51 Cleaning Ash removing USB Time window setting ...
Page 53: ...Automatic boiler for wood pellets 52 Load from USB Save on USB ...
Page 58: ...Automatic boiler for wood pellets 57 ...
Page 60: ...Automatic boiler for wood pellets 59 ...
Page 61: ...Automatic boiler for wood pellets 60 i ...
Page 63: ...62 Picture No 24 Principle of the modulation ...
Page 64: ...63 Picture No 25 Directory information consumption wood pellets for boiler family KP ...
Page 65: ...64 Picture No 26 Circuit diagram control unit ...
Page 66: ...65 Picture No 27 Circuit diagram module HZS 533 ...
Page 67: ...66 Picture No 28 Circuit diagram HZS 533 HZS 535 ...
Page 73: ...72 11 APPENDIX 2 REPORT ON THE PUTTING THE BOILER KP INTO OPERATION ...
Page 74: ...73 12 APPENDIX 3 SELF ADHESIVE LABEL IMPORTANT SAFETY INFORMATION ...