6.3 GOOSE publish
GOOSE publish is valid in Quick Test, Sequence and IED modules. The ASDU and
sample rate can be edited.
The GOOSE publish process is shown as below.
GOOSE configuration-> Add GOOSE block-> Set GOOSE parameter and channel->
choose the GOOSE block to be sent->Set voltage-> current or binary in QuickTest or
State Sequence->Set GOOSE publish and BI mapping channel-> Send or modify the
GOOSE channel->Get GOOSE result
The repetition, fast repeititions and GOOSE block can be edited here.
GOOSE publish
Max repeitition interval (second):
The default time is 5,000.
Fast repetitions T1 (minute):
Set GOOSE time interval T1 and default value 2.
PNS630 will make GOOSE publish as below diagram. When there is bit-change during
GOOSE data transmission, it will re-send GOOSE messages in total 5 frames. When the
bit-change begins, it starts sendng the 1
st
frame. The 2
nd
and 3
rd
frame will be sent with
interval of T1. Then the 4
th
frame will be sent at interval of T2. Lastly, the 5
th
frame will be
sent at interval of T3. Finally the new cycle will begin at interval of T0.