PNS630 Handheld Analyzer User Manual
9
2.2 Performance
1) Dynamic response time < 2s
2) Remote measurement response < 2s
3) Remote information response time < 2s
4) Transimission distance > 1km
,
output accuracy 0.5 class
5) The average largest error of sending SMV < 1us.
6) 30.0Hz~70.0Hz:
SMV voltage: 0.01Ue~2Ue, measurement accuracy > 0.05% and phase accuracy >
0.01°.
SMV current: 0.01Ie~40I, measurement accuracy > 0.05% and phase
accuracy >0.01°, frequency accuracy > 0.002Hz.
7) Resolution of GOOSE receiving < 1ms
8) Error
≤1us in IRIG
-B mode
9) Measurement range of the optical power -31dbm~-14dbm, wavelength 1310nm
10) Support SCL import.