9.6.1 Configuring relays in mode 1:
In the above example, the relays are configured as indicated below:
Use the
and
keys to
increase the values.
Use the
and
keys to
navigate the selections.
Configure the two relays and press ENTER.
CONFIG
MODE 1: ADJUSTMENT OF THE
THRESHOLDS AND HYSTERESIS
Rel 1 connected to SS measurement:
Alarm threshold: 2.01g/l Hyst: 0.10g/l
Above
the threshold, R1 is on
Rel 2 connected to temperature measurement:
Alarm threshold:20.01°C Hyst: 0.06°C
Above the threshold, R2 is on
ESC: Cancel the procedure
Enter: Validate the choice
CONFIG
WHAT DO YOU WANT TO DO?
Averaging sensor response
Sludge slope coefficient reminder
Sensor offset adjustment
Graphic screen
4-20mA outputs adjustment
Relay adjustment
Measure units
Language
Factory default value reminder
ESC: Escape menu
Comment: Both relays are
configured correctly in
mode 1.
2.01
1.91
R1
20.01
19.95
R2
SS
(g/l)
Temperature
Alarm
threshold
Hysteresis
Hysteresis
Alarm
threshold
Inactive
Inactive
Inactive
Inactive
Active
Active
Active
Active