User manual
PONSEL
Référence : NOTICE_ACTEON_2050_v001
V : 002
53/67
9.6.2 Configuring relays in mode 2:
In the above example, the relays are configured as indicated below:
Use the
and
keys to
increase the values.
Use the
and
keys to
navigate the selections.
Configure the two relays and press ENTER.
CONFIG
MODE 2: ADJUSTMENT OF THE
THRESHOLDS AND HYSTERESIS
Rel 1 connected to SS measurement:
Alarm threshold: 2.01g/l Hyst: 0.10g/l
Below
the threshold, R1 is on
Rel 2 connected to SS measurement:
Alarm threshold: 4.51g/l Hyst: 0.10g/l
Above the threshold, R2 is on
ESC: Cancel the procedure
Enter: Validate the choice
Comment: Both relays are
configured correctly in
mode 2.
CONFIG
WHAT DO YOU WANT TO DO?
Averaging sensor response
Sludge slope coefficient reminder
Sensor offset adjustment
Graphic screen
4-20mA outputs adjustment
Relay adjustment
Measure units
Language
Factory default value reminder
ESC: Escape menu
4.51
4.41
R1
R2
2.01
1.91
Alarm
threshold
R2
Hysteresis
Hysteresis
Alarm
threshold
R1
Inactive
Active
Inactive
Inactive
Inactive
Active
Active
Active
SS
(g/l)