In the above example, the relays are configured as indicated below:
Comment:
In mode 3, the high threshold must always be 1g/l higher than the low threshold.
During forced shutdown delay, the relay remains open regardless of the measured SS value.
During forced start-up delay, the relay remains open regardless of the measured SS value.
1.50
R1
0.50
SS
(g/l)
The SS value must go beyond the high threshold for at least 45 sec.
Forced start-up delay
10 min
The SS value must go beyond the low threshold for at least 45 sec.
3 min
Inactive
Inactive
Active
Active
1
1
2
2
3
3
4
Forced shutdown delay
4