5. MAINTeNANCe ANd INSPeCTION
5.1 Maintenance and Inspection
You should eliminate causes of prime loss and ensure unrestricted water flow. Clear debris from the pool/spa and pump
baskets regularly to avoid damage to the heat pump. Ensure the area around the heat pump is well ventilated and free
from debris and flooding. The evaporator/condenser should be well maintained at all times with no obstructions that will
affect the heat pumps performance.
WARNING: If debris such as leaves accumulate inside the unit, they could block the drain hole and cause corrosion to the
heat pump.
A refrigeration mechanic should be employed to do periodic maintenance to the heat pump, including cleaning the
condenser, checking gas levels and removing debris from inside the unit.
NOTE:
Should the heat pump start working abnormally, switch it off and contact your authorized Poolrite technician.
If the heat pump is not to be used for an extended period of time then isolate power to the unit, and empty the heat
exchanger of water. This will avoid internal damage to the heat exchanger. It is advised to flush the heat exchanger with
non chlorinated fresh water or town water.
NOTE:
The heat pump must be fully charged with water before power is restored, to avoid any damage to the unit.
5.2 Malfunction Guide
LCD CONTROLLER
MALFUNCTION
RESOLUTION
PP01
Water inlet temperature sensor failure
Check for water contamination or damaged wiring.
Repair or change as necessary
PP02
Water outlet temperature sensor failure
Check for water contamination or damaged wiring.
Repair or change as necessary
PP03
Coil 1 sensor 1 failure
Check for water contamination or damaged wiring.
Repair or change as necessary
PP04
Coil 2 sensor 2 failure
Check for water contamination or damaged wiring.
Repair or change as necessary
PP05
Ambient temp.Sensor failure
Check for water contamination or damaged wiring.
Repair or change as necessary
PP06
Temp. Difference between in and out is too great
Check water flow rate, eliminate obstructions,clean filters etc.
Adjust bypass flow as necessary
PP07
Anti freezing of heat exchanger
Check water flow volume
PP08
Ambient freezing protection
Ambient temp. Too low
PP09
Ambient freezing protection
Ambient temp. Too low
EE01
Malfunction of system 1
Check protection point of system 1.
Check temperature and gas pressures
EE02
Malfunction of system 2
Check protection point of system 2.
Check temperature and gas pressures
EE03
Flow switch failure or not enough flow
Check flow or replace flow switch
EE04 (55 + 62KW)
Incorrect phase configuration
Reconfigure phase connection
EE04 (12/16/26/32 KW)
Gas charge too low or high or system blocked
Check pressure switches or gas levels
EE05
Difference between water in and out temp too high
Eliminate obstructions. Clean filter etc.
Adjust bypass flow as necessary
EE08
Communication failure
Check lcd controller and pcb connection
No Display(26/32 KW)
Incorrect phase configuration
Reconfigure phase connection