Send Unsolicited temperature report (Parameter Number 1, Parameter Size 1) Threshold temperature to
send unsolicited report. 10 = 1 °C
Value
Description
0
Disabled (Default)
5 — 50 0.1 °C
Temperature shift (Parameter Number 2, Parameter Size 1) Threshold correction. For positive value 10 = 1
°C, for negative value x = 256 - (T°C * 10). Example, if need shift -2°C, value calculate: 256 - (2 * 10) = 236.
Value
Description
0
Disabled (Default)
1 — 127
0.1 °C
127 — 255 0.1 °C
Inverts Switching Command on Association Group 2 (Parameter Number 5, Parameter Size 1)
Value
Description
0
At High send ON (Default)
255
At High send OFF
Inverts Switching Command on Association Group 4 (Smoke) (Parameter Number 7, Parameter Size 1)
Value
Description
0
on Smoke send ON (Default)
255
on Smoke send OFF
Send SensorBinary- Report to Group 1 (Parameter Number 8, Parameter Size 1) When Smoke is detected
a Sensor Binary Report is sent out to Association Group 1
Value
Description
255
Send Alarm Smoke
0
Send Sensor Binary Report (Default)
Temperatur Trigger Low Value (Parameter Number 9, Parameter Size 1) Needs parameter ?1 to be set.
Sets the temperature Low value, if the measurement is lower than this value, Basic OFF is sent in
temperature association group(2). 255 -disable
(c) 2012 Z-Wave Europe GmbH, Goldbachstr. 13, 09337 Hohenstein-Ernstthal, Germany, All rights reserved, www.zwaveeurope.com - pp 6