Report the current when the current has changed by more then X *0,01 A. When disabled the
device will report every 10 minutes regardless of current change.
Size: 1 Byte, Default Value: 10
Setting
Description
0
Disabled
1 - 255
* 0,01 A
Parameter 25: Power Reporting Threshold
Report the power when the power has changed by more then X Watt. When disabled the
device will report every 10 minutes regardless of power consumption change.
Size: 1 Byte, Default Value: 50
Setting
Description
0
Disabled
1 - 255
W
Parameter 26: Soft Circuit Breaker Threshold
When the power draw exceeds the value set in this parameter for a time set in parameter 28
the soft ciruit breaker will disconnect the load.
Size: 2 Byte, Default Value: 3600
Setting
Description
0
Disabled
1 - 3600
W
Parameter 27: Soft Circuit Breaker Recovery Time
Once the soft circuit breaker tipps and the load is disconnected the load will be automatically
reconneced after X seconds. When disabled the load must be repowered manually or with
wireless command.
Size: 1 Byte, Default Value: 0
Setting
Description
0
Never
1 - 255
sec.
Parameter 28: Soft Circuit Breaker Delay Time
This delay time defines how fast the soft circuit breaker wil react when the threshold power is
exceeded. The power is cut off only if the power draw remains over the threshold level for the
defines time.
Size: 1 Byte, Default Value: 10
Setting
Description
0 - 255
* 0,1 sec