2.5
INSTALLING THE STOVE USING TOP FLUE OUTLET WHEN
CHIMNEY HAS NO INTEGRAL CLAY FLUE LINER.
Fig. 4
11
Minimum effective
flue height
3.0 metres
Flue termination
to comply with
BS 5440-1
Register plate
5” / 125mm
Flexible flue
liner
5” / 125mm
flue liner
IMPORTANT NOTE : If the stove is fitted with a top flue outlet and the chimney does
not have an integral clay chimney liner then the flue should be lined with a flexible flue
liner as shown above.
A liner-less flue kit (part number 1188-1028579) can also be utilised on chimneys
without an integral clay liner providing the chimney is in good, sound condition and
does not exceed 10m in height on an external chimney or 12m in height on an internal
chimney. Alternatively, the stove can be fitted with the closure plate and a rear flue
outlet to unlined chimneys as shown in section 2.4 on the previous page.
Minimum 50mm side and
rear clearance to non
combustible or 450mm to
combustible
surfaces to be strictly
adhered to.
In the event of clearance
issues to a structural lintel
a cranked pipe kit is
available, please quote
part number
1188-1028590.
Usage of other cranked
pipe designs is not
permitted, only the
kit specified can be utilsed
for this installation
method. It may also be
necesssary to remove the
flue restrictor plate,
subject to spillage tests.