5401587 - REV B • 6/21
PAGE 7 OF 10
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
SignaLink
™
Bridge
Wireless Supervisory System
Battery
Compartment
EOLR from fire
panel zone
Battery
Com
Ext Power
Fig 2
Fig 3
POWER
COM
NO
24VDC
PWR
Low Battery
EOLR Error
WTX-M
WR
Alarm/Supervisory
Tamper
COM Error
Setup Mode
TX
+
24 VDC
-
Battery RST
Antenna area
Troubleshooting/
Learning LEDs
24 VDC Alternate
power input
Cover Tamper
Switch
Fig 1
WTX-M - Transmitter
WRX-R - Wireless Receiver
WR - Wireless Repeater
FACP ZONE OR MONITOR MODULE
The WRX-R contains a normally
energized, failsafe relay. Under normal
conditions, it internally connects the NO
terminal and the EOLR resistor symbol
terminal. A loss of power or any trouble
condition causes the relay to drop out
and open the EOLR circuit, this creates
a trouble on the fire panel.
24 VDC at 55mA
From AUX power of FACP or other listed
source with battery backup.
Power source jumper
Batt Reset
TX
Two flying leads from WTX-M.
Connect to Normally Open
contacts of device to be
monitored. Also install the
supplied 5.1k ohm End Of Line
Resistor across the Normally
Open contacts.
Cover Tamper Switch
Battery Compartment
Antenna area
1/2” threaded nipple connects
directly through conduit opening
of sprinkler switch. O-ring
provides weatherproof seal
Troubleshooting / Learning LEDs.
BATTERY RESET
TRANSMIT TX
All batteries in a device must be replaced at the same time and
with the battery type specified in this document.