 INSTALLATION MANUAL: PAD100-SLCE ADDRESSABLE LOOP EXPANDER

Document 5406314-A  02/16

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 2 OF 2

Before connecting a device to the RS-485 connection, take the following precautions to prevent potential damage to the RS-485 

connection or device.

• 

Power to the RS-485 is removed.

• 

Field wiring on module is correctly installed.

• 

Field wiring has no open or short circuits.

3. 

Technical Specifications

Standby Current

50mA

Alarm Current

50mA

SLC Voltage

24 VDC

Max. SLC Resistance

50 Ohms

P-Link Voltage

24 VDC

Operating Temperature Range

32

̊ 

to 120

̊ 

F (0

̊ 

to 49

̊ 

C)

Operating Humidity Range

10% to 93% (non-condensing)

Max. no of PAD100-SLCE

31

Dimensions

4" L x 6" W x 1 5/8" D

4.  Installation

The PAD100-SLCE is connected to the listed control panels using a four wire RS-485 connection. This connection is power limited 

and supervised. The PAD100-SLCE can be installed in the AE-2, AE-8, AE-14 expansion enclosure or inside the large listed fire 

alarm control panel enclosure using the supplied bracket. The wiring diagrams shown below illustrate how to wire a PAD100-SLCE 

as Class B and Class A.

Figure 3. Examples of Wiring a PAD100-SLCE P-Link Class B & Class A Wiring

Notes:

• 

RS-485 wiring style supports the Class A and Class B.

• 

RS-485 wiring is power limited and supervised.

• 

All wiring is between #12 (max.) and #22 (min.).

• 

Wire Preparation – Strip all wires 1/4 inch from their edges as shown here: 

– Stripping too much insulation may cause a ground fault.

– Stripping too little may cause a poor connection and subsequently an open circuit.

These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every 

possible contingency to be met in connection with installation, operation and maintenance.

Specifications subject to change without prior notification.
For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.
Actual performance is based on proper application of the product by a qualified professional.
Should further information be desired or should particular problems arise, which are not covered sufficiently for the 

purchaser's purpose, the matter should be referred to a distributor in your region.

1/4 inch

-

   

   

   

  B

Expansion 

Device

-

   

   

A

   

   

B

P-LINK

-

+        A        B

P-LINK

-

+        A        B

Panel

Connection

Class A

Expander

Connection

Expansion 

Device

To the next  device

-

   

   

A

   

   

B

Expansion 

Device

-

   

   

   

  B

P-LINK

-

+        A        B

Panel

Connection

Expansion 

Device