INSTALLATION MANUAL:  PAD100-ZM ZONE MODULE

Document 5406308

-A  02/16

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 4 OF 4

Table 1: Compatible Conventional Smoke Detectors & Bases

Detector Model

Identifier

Base Model

Identifier

System Sensor (Brk) (Max. No. Of Detectors Per Zone is 10)

1400

A

N/A

N/A

2400

A

N/A

N/A

2400TH

A

N/A

N/A

2W-B

A

N/A

N/A

2WT-B

A

N/A

N/A

Detection System (Max. No. Of Detectors Per Zone is 11)

DS250

A

MB2W/MB2WL

A

DS250TH

A

MB2W/MB2WL

A

ESL (Max. No. Of Detectors Per Zone is 20)

611U

S10

601U

S00

611UD

S10

601U

S00

611UT

S10

601U

S00

612U

S10

601U

S00

612UD

S10

601U

S00

613U5

S10

601U

S00

611UD

S10

609U10

S00

612UD

S10

609U10

S00

425C

S10

N/A

N/A

425CT

S10

N/A

N/A

HOCHIKI (Max. No. Of Detectors Per Zone is 20)

SLR-24

HD-3

HSC-221R

HB-71

HSB-221

HB-54

HSB-221N

HB-54

NS6-221

NS4-221

NS6-220

HB-3

SLR-24H

HD-3

HSC-221R

HB-71

HSB-221

HB-54

HSB-221N

HB-54

NS6-221

NS4-221

SIJ-24

HD-3

HSC-221R

HB-71

HSB-221

HB-54

HSB-221N

HB-54

NS6-221

NS4-221

FENWAL (Max. No. Of Detectors Per Zone is 14)

CPD-7051

151FE1

2-WIRE

FE51A

PSD-7155

P55FE1

2WRLT

FE52A

PSD-7156

P56FE1

2WRB

FE55A

All of the above Fenwal detectors and bases can be used in any combination.

Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001,-002,-003 and -005).

Duct Housing with Detector Base DN-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).

POTTER (Max. No. Of Detectors Per Zone is 25)

PS-24

HD-3 (HOCHIKI)

SB-46

HB-71 (HOCHIKI)

HB-54 (HOCHIKI)

SB-93

HB-3 (HOCHIKI)

PS-24H

HD-3 (HOCHIKI)

SB-46

HB-71 (HOCHIKI)

HB-54 (HOCHIKI)

IS-24

HD-3 (HOCHIKI)

SB-46

HB-71 (HOCHIKI)

HB-54 (HOCHIKI)

NOTE: 

If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.

firealarmresources.com

Summary of Contents for PAD100-ZM

Page 1: ...ndition the LED of the device will be off All other conditions remain the same 2 Setting the Address All PAD protocol detectors and modules require an address prior to connection to the panel s SLC loop Each PAD device s address i e detector and or module is set by changing the dip switches located on the device PAD device addresses are comprised of a seven 7 position dip switch used to program ea...

Page 2: ...ng Voltage 24 0V Max SLC Standby Current 240 μ A Max SLC Alarm Current 240 μ A Aux Power Required 19 28V Max Detector Standby Current of IDC at 24 VDC 1mA Max Module Alarm Current of IDC at 24 VDC 50mA Max Wiring Resistance of IDC 100 Ω Max Wiring Capacitance of IDC 1μF Smoke Detector Compatibility Identifier A EOL Resistor 5 1K Ω Operating Temperature Range 32 to 120 F 0 to 49 C Operating Humidit...

Page 3: ... the details or variations in the equipment described nor provide for every possible contingency to be met in connection with installation operation and maintenance Specifications subject to change without prior notification For Technical Assistance contact Potter Electric Signal Company at 866 956 1211 Actual performance is based on proper application of the product by a qualified professional Sh...

Page 4: ...3 HSC 221R HB 71 HSB 221 HB 54 HSB 221N HB 54 NS6 221 NS4 221 NS6 220 HB 3 SLR 24H HD 3 HSC 221R HB 71 HSB 221 HB 54 HSB 221N HB 54 NS6 221 NS4 221 SIJ 24 HD 3 HSC 221R HB 71 HSB 221 HB 54 HSB 221N HB 54 NS6 221 NS4 221 FENWAL Max No Of Detectors Per Zone is 14 CPD 7051 151FE1 2 WIRE FE51A PSD 7155 P55FE1 2WRLT FE52A PSD 7156 P56FE1 2WRB FE55A All of the above Fenwal detectors and bases can be use...

Reviews: