2-9
PFC-6030 • 5403595 • REV C-1 • 10/13
SLC Current Draw Worksheet
Device Type
Qty
Standby
(mA)
Total
Standby
(mA)
Alarm
(mA)
Total
Alarm
(mA)
Analog photo smoke detector (PSA)
0.325
0.325
Analog photo DUCT smoke detector (DSA)
0.325
0.325
Analog photo smoke / fixed heat detector (PSHA)
0.325
0.325
Analog fixed heat detector (FHA)
0.325
0.325
Analog combo heat detector (RHA)
0.325
0.325
Conventional initiating zone module - 4 inch mount (CIZM-4) *Note 1
0.325
1.000
Miniature contact module (MCM)
0.325
0.325
Single contact module - 4 inch mount (SCM-4)
0.325
1.000
Dual contact module - 4 inch mount (DCM-4)
0.325
1.000
Monitored output module - 4 inch mount (MOM-4) *Note 2
0.325
1.000
Twin relay module - 4 inch mount (TRM-4)
0.325
1.000
Short circuit isolator (SCI)
0.325
2.34
Analog sounder base (ASB) *Note 3
0.325
0.325
Analog relay base (ARB) *Note 4
0.325
0.325
Isolator base (AIB)
0.325
2.34
SLC alarm LED Current
n/a
n/a
n/a
27.0
SLC Standby
Current
SLC Alarm
Current
* Note 1: CIZM requires 24VDC power source. Standby current Style D = 4.90 mA, Style B (8.5 mA). Alarm Current = 50.0 mA
* Note 2: MOM requires 24VDC power source. Standby current = 1.60 mA. Alarm Current = 1.60 mA
* Note 3: ASB requires 24VDC power source. Standby current = 5 mA. Alarm Current = 100 mA
* Note 4: ARB requires 24VDC power source. Standby current = 5 mA. Alarm Current = 50 mA