FIB-1000 Wiring
FIB-1000s are installed in pairs. (
Please refer to Diagrams #1 & 2 shown below to properly wire the two FIB-1000s.)
The first
FIB-1000, referred to as
"FIB-1000 (A)"
below
can be installed in any of the compatible fire alarm enclosures, or the FIB-
1000RM. It is connected via the
4-wire P-Link connection
.
Set
S2
on FIB-1000 (A) to the "OFF" position,
which provides an
outgoing fiber option connection
. That fiber optic connection can be connected as
Class A or Class B
to the second FIB-1000,
referred to as
"FIB-1000 (B)"
below.
The second FIB-1000 (B) is installed in a
PSN-1000E
(
shown in Diagram #2 below
).
Set S2 on FIB-1000 (B) to the "ON"
position.
It then provides an
outgoing P-Link connection
. Connect the
4-wire P-Link on the FIB-1000 (B)
to the
P-Link
connection on the PSN-1000E
.
To power the FIB-1000 (B), connect the
24VDC "+" and "-" terminals
on PSN-1000E (
shown in Diagram #2 below
) to the
isolated P -Link 24 VDC "+" and "-" terminals
. The
PSN-1000E's isolated P-Link
can now be used to connect any other
P-Link appliance, including the RA-1000, LED-16, and PSN-1000/PSN-1000E.
Figure 45. Diagram #1: FIB-1000 Wiring Diagram Showing Detail
Figure 46. Diagram #2: FIB-1000 Wiring Diagram Shown Installed in PSN-1000E Cabinet
Master Panel or PSN1000E
P-LINK
PSN-1000
B
A
+
-
B
A
+
-
To Additional
P-Link Devices
B
A
+
-
S1
S2
ON
OFF
-
+
A
B
S2
S1
ON
OFF
FIB-1000 (A)
Upstream FIB
S2 = OFF
S2 =
OFF
FIB-1000 (B)
Downstream FIB
S2 = ON
ON
R x 2
T x 2
R x 1
T x 1
T x 1
R x 1
T x 2
R x 2
Fiber Optic
Cable
OUT
IN
DWG #608-25B
PSN-1000E
B
A
+
-
B
A
+
-
T1
R1
R2 T2
B
A
+
-
FIB-1000 (B)
To Additional
P-Link Devices
Fiber In
DWG #608-25A