5-43
PFC-6030 • 5403595 • REV C-1 • 10/13
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
SLC Point
Alarm Verif
Y
Yes/No
All settings allowed
SLC Point
Supervisory
Y
Yes/No
All settings allowed
NACs
Function
Potter/Amseco Sync
Gentex Sync
System Sensor Sync
Wheelock Sync
Constant Output
Resettable Output
Door Holder Output
ANSI Output
City Tie Output
All settings allowed
Specifies use of
NAC circuit(s)
Day/Night
Smoke Sensitivity
Y
Full listed range of
smoke detector
All settings allowed
Up to 50 holidays where
day mode is not active.
DACT
Daily Test Call
Y
Any time of day
All settings allowed
Alternates between line
1 and 2 if line 2
is enabled.
E-mail Status
Reports
N
Alarms, Troubles, Supervisory
Test, History & Status Reports
IP-Dialer
IP Based Central
Station Reporting
Y
Alarms, Supervisory,
Trouble & Test Reports
All settings allowed