Installation Requirements - Page 15
1.11 Clearances around the Appliance.
Side Clearance:
The position selected for the appliance must provide the
following minimum clearance which is necessary for
operation and servicing, 25mm each side (side
clearances have been incorporated into template).
Top Clearance:
The top clearance should be a minimum of 160mm, but
300mm is preferred to allow removal of the central
heating expansion vessel, without removing the
appliance from the wall, if replacement is required.
Bottom Clearance:
A bottom clearance of 220mm is required between the
appliance and any surface.
Frontal Clearance:
A minimum of 500mm is required in front of the
appliance for access during servicing, the front
clearance can be reduced providing the door/cover can
be removed to expose the entire case front.
Summary of Contents for 80e
Page 5: ...Optional Extras Page 5 ...
Page 6: ...Optional Extras Page 6 Installation instructions included as necessary with each kit ...
Page 7: ...Optional Extras Page 7 Installation instructions included as necessary with each kit ...
Page 12: ......
Page 28: ...Routine Maintenance Page 27 ...
Page 30: ...Routine Maintenance Page 29 ...
Page 34: ...Component Replacement Page 33 ...
Page 35: ...Component Replacement Page 34 ...
Page 43: ...7 1 Control Flow Sequence Permanent Pilot Page 42 ...
Page 44: ...7 2 Functional Flow Permanent Pilot Page 43 ...
Page 45: ...7 3 Fault Finding Permanent Pilot Page 44 ...
Page 46: ...7 4 Electrical Diagram Permanent Pilot Page 45 ...
Page 47: ...8 1 Control Flow Sequence Electronic Page 46 ...
Page 48: ...8 2 Functional Flow Electronic Page 47 ...
Page 49: ...8 3 Fault Finding Electronic Page 48 ...
Page 50: ...8 4 Electrical Diagram Electronic Page 49 ...