Time program 5
Prog. no.
Level Standard value
1st phase off
602
Eu
22:00 (h/min)
2nd phase on
603
Eu
--:-- (h/min)
2nd phase off
604
Eu
--:-- (h/min)
3rd phase on
605
Eu
--:-- (h/min)
3rd phase off
606
Eu
--:-- (h/min)
Copy?
615
Eu
Default values
No | Yes
616
Eu
No
Holiday
Heating
circuit 1
Prog. no.
Heating
Prog. no.
Heating
circuit 3
(1)
Prog. no.
Level Standard value
Preselection
Period 1 | Period 2 | Period 3 | Period 4 | Period 5 |
Period 6 | Period 7 | Period 8
641
651
661
Eu
Period 1
Start
642
652
662
Eu
—.— (day.month)
End
643
653
663
Eu
—.— (day.month)
Operating level
Protection | Reduced
648
658
668
Eu
Protection
(1) Parameter only visible if heating circuit exists!
Heating circuit
1
Prog. no.
Prog. no.
3
(1)
Prog. no.
Level Standard value
Operating mode
Protection | Automatic | Reduced | Comfort
700
1000
1300
Eu
Automatic
Comfort setpoint
710
1010
1310
Eu
20.0 °C
Reduced setpoint
712
1012
1312
Eu
18 °C
Frost protection setpoint
714
1014
1314
Eu
10.0 °C
Heating curve slope
720
1020
1320
Eu
1,24
Heating curve displacement
721
1021
1321
E
2.0 °C
Heating curve adaption
0: Off | 1: On
726
1026
1326
E
Off
Summer/winter heating limit
730
1030
1330
Eu
20°C
24-hour heating limit
732
1032
1332
E
0 °C
Flow temp setpoint min
740
1040
1340
E
8 °C
Flow temp setpoint max
741
1041
1341
E
80 °C
Flow temp setpoint room stat
742
1042
1342
E
- - - °C
Swi-on ratio room stat
744
1044
1344
E
- - - %
Delay heat request
746
1046
1346
E
0 s
Room influence
750
1050
1350
C
- - - %
Room temp limitation
760
1060
1360
E
0.5 °C
Boost heating
770
1070
1370
E
- - - °C
Quick setback
0: Off | 1: To Reduced setpoint | 2: To Protection
setpoint
780
1080
1380
E
1: To Reduced
setpoint
Optimum start control max
790
1090
1390
E
0 (h:min)
Optimum stop control max
791
1091
1391
E
0 (h:min)
Reduced setp increase start
800
1100
1400
E
- - - °C
Reduced setp increase end
801
1101
1401
E
-15 °C
Continuous pump operation
0: No | 1: Yes
809
1109
1409
E
0: No
Overtemp prot pump circuit
0: Off | 1: On
820
1120
1420
E
0: Off
Mixing valve boost
830
1130
1430
E
5 °C
Actuator running time
834
1134
1434
E
140 s
9 Settings
62