Solar
Prog. no.
Level Standard value
Charging time relative prio
3825
E
- - - min
Waiting time relative prio
3826
E
5 min
Waiting time parallel op
3827
E
- - - min
Delay secondary pump
3828
E
60 s
Collector start function
3830
E
- - - min
Min run time collector pump
3831
E
20 s
Collector start function on
3832
E
07:00 (h:min)
Collector start function off
3833
E
19:00 (h:min)
Collector start funct grad
3834
E
- - - min/°C
Collector frost protection
3840
E
- - - °C
Collector overtemp prot
3850
E
- - - °C
Evaporation heat carrier
3860
E
130 °C
Pump speed min
3870
E
10 %
Pump speed max
3871
E
100 %
Antifreeze
1: None | 2: Ethylene glycol | 3: Propylene glycol | 4: Ethyl and propyl glycol
3880
E
3: Propylene glycol
Antifreeze concentration
3881
E
50 %
Pump capacity
3884
E
200 l/h
Pulse unit yield
3887
E
10 l
Solid fuel boiler
Prog. no.
Level Standard value
Locks other heat sources
0: Off | 1: On
4102
E
0: Off
Setpoint min
4110
E
65 °C
Temp diff on
4130
E
8 °C
Temp diff off
4131
E
4 °C
Comparative temp
1: DHW sensor B3 | 2: DHW sensor B31 | 3: Buffer sensor B4 | 4: Buffer sensor
B41 | 5: Flow temp setpoint | 6: Setpoint min
4133
E
Buffer sensor B41
Pump overrun time
4140
E
20 min
Buffer storage tank
Prog. no.
Level Standard value
Auto generation lock
0: None | 1: With B4 | 2: With B4 and B42/B41
4720
E
1: With B4
Auto heat gen lock SD
4721
E
5 °C
Temp diff buffer/HC
4722
E
-3 °C
Min st tank temp heat mode
4724
E
- - - °C
Charging temp max
4750
E
80 °C
Recooling temp
4755
E
60 °C
Recooling DHW/HCs
0: Off | 1: On
4756
E
0: Off
Recooling collector
0: Off | 1: Summer | 2: Always
4757
E
0: Off
With solar integration
0: No | 1: Yes
4783
E
1: Yes
Temp diff on return div
4790
E
8 °C
Temp diff off return div
4791
E
4 °C
Compar temp return div
1: With B4 | 2: With B41 | 3: With B42
4795
E
1: With B4
Optg action return diversion
1: Temp decrease | 2: Temp increase
4796
E
2: Temp increase
Partial charging setpoint
4800
E
- - - °C
Full charging
0: Off | 1: Heating mode | 2: Always
4810
E
0: Off
9 Settings
7703301 - 01 - 16072018
67