Water pressure min (6181)
A maintenance message is indicated from this set water pressure. The
boiler output is reduced by 20% to protect the boiler. The message is only
reset when the set pressure has been exceeded by 0.2 bar.
Save sensors (6200)
Sensor modes can be saved under prog. no. 6200. This is done
automatically; however, after change of the heating system (removal of a
sensor) the state must be saved again to the sensor terminals.
Reset to default parameters (6205)
The factory setting of the regulator is written to the regulator.
Caution
The regulator parameters are overwritten. The factory settings are
stored in the regulator.
Activation of prog. no. 6205:
The regulator is reset to factory setting.
Check no. heat source 1 (6212), Check no. heat source 2
(6213), Check no. storage tank (6215) and Check no. heating
circuits (6217)
The standard device generates a check number to identify the system
scheme; this comprises the numbers listed in the table below.
Tab.16 Check no. storage tank (prog.-no. 6215)
Domestic water storage tank
No buffer storage tank
0
No DHW storage tank
Buffer storage tank
1
Immersion heater
Buffer storage tank, heat generation shutoff valve
4
Primary pump
Buffer storage tank, solar connection, source shut-off
valve
5
Charging pump, solar connection
13
Diverter valve
16
Primary controller, without heat exchanger
17
Primary controller, 1 heat exchanger
Tab.17 Check no. heating circuit (prog.-no. 6217)
Heating circuit 3
Heating circuit 2
Heating circuit 1
0
No heating circuit
00 No heating circuit
00 No heating circuit
1
DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
2
Heating circuit pump
02 Heating circuit pump
02 Heating circuit pump
3
Heating circuit pump, mixer
03 Heating circuit pump, mixer
03 Heating circuit pump, mixer
Software version (6220)
Display of the actual software version.
Info 1 OEM(6230), Info 2 OEM (6231), Info 3 OEM (6258), Info
4 OEM (6259) and Parameter set number OEM (6236)
These parameters are EEPROM storage locations that may contain
information from the OEM.
9.2.18 LPB system
Device address (6600) andSegment address (6601)
The two-part LPB address of the controller consists of the 2-digit segment
number and the 2-digit device number.
9 Settings
7703301 - 01 - 16072018
119