Function
Prog. no.
Setting level
EC five
125 kW
EC five
170 kW
EC five
215 kW
Natural
gas
Propane Natural
gas
Propane Natural
gas
Propane
Boiler
Output basic stage
2331
E
20
35
28
35
35
48
Burner control
Required output prepurging
9504
E
100
100
120
120
100
100
Required output ignition
9512
E
59.3
66.3
75.5
86.8
77.1
89.3
Required output LF
9524
E
20.0
35.0
28.0
35.0
35.0
48.0
Fan output/speed slope
9626
E
37.1
33.9
27.6
24.1
26.4
23.0
Fan output/speed Y-section
9627
E
501.1
453.9
517.2
507.4
464.4
446.3
CO
2
content (± 0.2)
9.3
11.0
9.3
11.0
9.3
11.0
Function
Prog. no.
Setting level
EC five
260 kW
EC five
300 kW
Natural gas
Propane
Natural gas
Propane
Boiler
Output basic stage
2331
E
42
58
48
58
Burner control
Required output prepurging
9504
E
180
180
170
170
Required output ignition
9512
E
93.4
110.0
103.9
115.5
Required output LF
9524
E
42.0
58.0
48.0
58.0
Fan output/speed slope
9626
E
20.1
19.9
19.9
19.0
Fan output/speed Y-section
9627
E
488.0
305.7
431.7
306.1
CO
2
content (± 0.2)
9.3
11.0
9.3
11.0
Caution
Risk for the environment and the device if CO content is too high!
When a boiler set for natural gas is put into operation with LPG,
the adjustment screw for full load on the gas valve must be turned
clockwise (-) by half a turn before the boiler is switched on!
7.4.4
Manual adjustment of burner output (controller stop
function)
For controlling the CO
2
values theEC five operated in the control stop
function
1. Press button Operating mode button heating operation for approx 3 s
The message Controller stop active is displayed.
2. Wait until the display has reached the basic display again.
3. Press the Info button
The message Controller stop setpoint appears on the display. The
actual modulation degree will be displayed on the display.
4. Press OK.
The setpoint can now be changed.
5. Press OK.
The setpoint displayed is then adopted by the controller.
Important
The regulator stop function is stopped by pressing the operating
mode button Heating Operation for approximately 3 seconds,
reaching the maximum boiler temperature or a time limit.
If there is demand for heat from a coiled tubing storage tank, this
demand will continue to be met during the controller stop function.
xxxxxxxxxxxxxx
7 Commissioning
52