Setpoint source heating (2056)
When using the generator heating, the swimming pool is heated to the
setpoint set here.
Charging priority solar (2065)
Setting of which priority the swimming pool will be solar heated. The
priority for the DHW and charging buffer is set under Prog. no. 3822.
Priority 1: Charging the swimming pool has top priority.
Priority 2: Charging the swimming pool has middle priority (between the
domestic water and the buffer storage tank).
Priority 3: Charging the swimming pool has lowest priority (after the
domestic water and the buffer storage tank).
Important
Release and priority can also be affected by the Hx inputs (see
also program no. 3822).
Swimming pool temp max (2070)
If the swimming pool temp reaches the heating limit set here, the collector
pump is switched off. It is again released if the swimming pool temp has
dropped by 1°C below the maximum heating limit temperature.
With solar integration (2080)
Setting, of whether the swimming pool heating can be done by solar
energy or not.
9.2.10 Primary contr/system pump
The primary controller enables the flow temperature to be mixed up or
down for heatinggroups with flow temperature setpoints that are lower or
higher than the temperature present on the rail. The feed pump can
overcome the pressure drop to heatinggroups that are further away.
Flow temp setpoint min (2110) and Flow temp setpoint max
(2111)
With these boundaries a range for the flow setpoint can be defined.
Syst pump on heat gen lock (2121)
This parameter can set whether the system pump is also locked or not
when the generator lock is active.
Off: The system pump is not locked.
On: When the generator lock is active the system pump is also locked.
Mixing valve boost (2130)
For the admixture the boiler flow temperature actual value must be higher
than the requested setpoint of the mixer flow temperature, since this
cannot be corrected otherwise. The controller forms the boiler temperature
setpoint from the boost set here and the current flow temperature setpoint.
Actuator running time (2134)
Setting the actuator running time of the mixing valve used.
Primary contr/system pump (2150)
Before buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically upstream of the buffer storage tank.
After buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically downstream of the buffer storage tank.
9.2.11 Boiler
Release below outside temp (2203)
The boiler is only put into operation if the mixed outside temperature is
below the threshold set here. The switching difference is 0.5°C.