All CHs in segment: DHW heating applies to all heating circuits in this
section.
All CHs in system: DHW heating applies to all heating circuits in the sys
tem.
Note
For all settings the controllers which are in holiday status are also
taken into account for the DHW preparation.
Clock mode (6640)
This setting determines the effect of the system time on the controller time
setting. The following settings are possible:
Autonomously: The time can be adjusted at the controller. The time of
the controller is not adapted to the system time.
Slave without remote setting: The time cannot be adjusted at the con
troller. The controller time is constantly synchronised to the system time.
Slave with remote setting: The time can be adjusted at the controller.
The system time is synchronised simultaneously as the change is adop
ted by the master. The time of the controller is then continually adapted
to the system time.
Master: The time can be adjusted at the controller. The controller time is
defaulted to the system. The system time is adapted.
Outside temp source (6650)
In the LPB system only one single outside temperature sensor is necessa
ry. This delivers the signal via the LPB to the controllers without a sensor.
The first figure in the display is the section number, the second is the ap
pliance number.
9.2.19 Fault
Message (6700)
A current existing error in the system is displayed here in the form of an
error code.
Display SW diagnostic code (6705)
In case of a fault, the display fault is on permanently. In addition, the diag
nosis code is displayed on the display.
Burn ctrl phase lockout pos (6706)
Phase during which the fault occurred which led to the failure.
Reset alarm relay (6710)
An output relay QX, programmed as an alarm relay can be reset via this
setting.
Flow temp 1 alarm (6740),Flow temp 2 alarm (6741),Flow temp
3 alarm (6742),Boiler temp alarm (6743) andHot water charging
alarm (6745)
Setting the time after which a fault message will be triggered in case of
persisting deviation from temperature nominal and actual values.
Error history / Error codes (6800-6995)
The last 20 error messages with error codes and time of occurrence are
saved to the error memory.
9.2.20 Maintenance / special operation
Burner hours interval (7040)
Setting of the interval for maintenance of the burner.
Burn hrs since maintenance (7041)
Burner hours since the last maintenance.
9 Settings
7636047 - 02 - 24082015
117
Summary of Contents for eurocondense four 125 kw
Page 19: ...3 2 6 Wiring diagram Fig 3 Wiring diagram 3 Technical specifications 7636047 02 24082015 19 ...
Page 40: ...Fig 22 Legend for application examples part 2 5 Before installation 40 7636047 02 24082015 ...
Page 143: ...13 Appendix 13 1 Declaration of conformity 13 Appendix 7636047 02 24082015 143 ...
Page 146: ...Index 146 7636047 02 24082015 ...
Page 148: ...7636047 02 24082015 ...