Function
Prog.
no.
Level
1)
Standard value
Heating curve slope
1320
Eu
1.50
Heating curve displacement
1321
E
0.0°C
Heating curve adaption
Off | On
1326
E
Off
Summer/winter heating limit
1330
Eu
18°C
24-hour heating limit
1332
E
-3°C
Flow temp setpoint min
1340
E
8°C
Flow temp setpoint max
1341
E
80°C
Flow temp setpoint room stat
1342
E
65°C
Room influence
1350
C
20 %
Room temp limitation
1360
E
1°C
Boost heating
1370
E
5°C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
1380
E
Down to reduced set-
point
Optimum start control max
1390
E
0 min
Optimum stop control max
1391
E
0 min
Reduced setp increase start
1400
E
- - -°C
Reduced setp increase end
1401
E
-15°C
Continuous pump operation
No | Yes
1409
E
No
Overtemp prot pump circuit
Off | On
1420
E
ON
Mixing valve boost
1430
E
5°C
Actuator running time
1434
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
1450
E
Off
Floor curing setp manually
1451
E
25°C
Floor curing setp current
1455
E
0°C
Floor curing day current
1456
E
0
Excess heat draw
Off | Heating mode | Always
1461
E
Always
With buffer storage tank
No | Yes
1470
E
Yes
With prim contr/system pump
No | Yes
1472
E
Yes
Pump speed reduction
Operating level | Characteristic
1480
E
Characteristic
Pump speed min
1482
C
0 %
Pump speed max
1483
C
100 %
Curve readj at 50% speed
1488
E
33 %
Flow setp readj speed ctrl
No | Yes
1490
E
Yes
Operating level changeover
Frost protection | Reduced | Comfort
1498
E
Reduced
Programming
14
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10
Summary of Contents for Eurocondense three
Page 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Page 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Page 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...