Delete all devices
(140)
The radio connections to all devices will be cancelled under programme number
140.
Time programmes
Note:
The time programme 1 and 2 are always assigned to the respective heating
circuits (1 - 3) and only displayed if these heating circuits are present and also tur-
ned on in the menu
Configuration
(prog.-no. 5710 and 5715).
Time program 3 can be used for the Heating circuit 3, for the DHW and for the cir-
culation pump, depending on the setting, and is always displayed.
Time program 4 can be used for the DHW and for the circulation pump, depending
on the setting, and is always displayed.
Time program 5 is not assigned a function and can be freely used for any applicati-
on using an output QX.
Preselection
(500, 520, 540, 560, 600)
Selection of weekdays or week blocks. The week blocks (Mo-Su, Mo-Fr and Sa-Su)
are used as a setting aid. The times set there are only copied on the individual
weekdays and can be again changed in the individual weekdays as required.
The times of the individual weekdays are always critical for the heating program-
me.
Note:
When the set time of a day group is changed, this will automatically be ta-
ken over for all 3 on/off phases in this day group.
Heating phases
(501 to 506, 521 to 526, 541
to 546, 561 to 566, 601 to
606)
Up to three heating phases may be set per heating circuit, which will be activated
on the days, set under the
preselection
(prog.-no. 500, 520, 540, 560, 600). In the
heating phases, it will be heated at the set comfort setpoint. Outside the heating
phases, it will be heated at the reduced setpoint.
Note:
The time programmes are only activated in the operation mode “Automa-
tic“.
Default values
(516, 536, 556, 576, 616)
Setting of the default values given in the setting table
Notice for time programme 4 / TWW:
For comfort reasons, it is necessary that 2
heating phases will be set with a pause of at least 10 minutes! The first phase
must be before the first heating phase of the heating, BRÖTJE recommends a first
heating of the storage of 1 hour.
Holiday programmes
The heating circuits may be set to a selectable operation level with the holiday
programme during a certain holiday period.
The heating circuits may be set to a selectable operation level with the holiday
program during a certain holiday period.
Preselection
(641, 651, 661)
8 vacation periods can be selected with this preselection.
Start of holiday
(642, 652, 662)
Entering the holiday start
Programming
34
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10
Summary of Contents for Eurocondense three
Page 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Page 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Page 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...