Relay outputs QX1 - QX3 (5890 - 5892)
Relay outputs QX1/QX2/QX3
(5890 - 5892)
-
None
: Relay outputs deactivated.
-
Circulation pump Q4
: The connected pump serves as domestic hot water circu-
lation pump (see prog. no. 1660).
-
El imm heater DHW K6
: With the connected electrical immersion heater, the
DHW can be charged according to the operating side DHW storage operating li-
nes electrical immersion heater.
Note: The Operating mode is set under programme number 5060.
-
Collector pump Q5
: Connection of a circulating pump in case of solar collector
use.
-
Cons circuit pump VK1/2/3
: Connection of a pump at the input Q15/18/19 for
an additional consumer, which is requested via an Hx-input.
-
Boiler pump Q1
: the connected pump is used for recirculation of the boiler water.
-
Alarm output K10
: An occurring fault will be signalled with the alarm relay. The
contact will be closed with a delay time of 2 minutes. If no fault exists any more,
the contact opens without delay.
Note: The alarm relay can be reset without having the fault remedied (see prog.
no. 6710).
-
Heating circuit pump HC3 / Q20
: Activating the pump heating circuit HC3.
-
System pump Q14
: Connection of a system pump.
-
Heat gen shutoff valve Y4
: Connection of a changeover valve for hydraulic de-
coupling the heat generator from the rest of the heating system.
-
Solid fuel boiler pump Q10
: Connection of a circulating pump for the boiler cir-
cuit for connection to a solid fuel boiler.
-
Time program 5 K13
: The relay will be controlled by the time program 5 accor-
ding to the settings.
-
Buffer return valve Y15
:This valve must be configured for return temperature
increase/decrease or the buffer storage tank partial charging.
-
Solar pump ext exch K9
:here, the solar pump external exchanger K9 must have
been set for the external heat exchange.
-
Solar ctrl elem buffer K8
: if several exchangers are connected, the buffer storage
must be set at the respective relay output and the type of solar regulating unit
must be defined under prog.no. 5840.
-
Solar ctrl elem buffer K8
: if several exchangers are connected, the swimming
pool must be set at the respective relay output and the type of the solar regula-
ting unit must be defined in prog.no. 5840.
-
Cascade pump Q25
: Boiler pump in common for all boilers in a cascade.
-
St tank transfer pump Q11
: The drinking water storage can be charged from the
buffer storage, if is sufficiently hot. This transfer is carried out with the transfer
pump Q11.
-
DHW mixing pump Q35
: Separate pump for storage circulation during active le-
gionella function.
-
DHW interm circ pump Q33
: pump for domestic hot water storage with external
heat exchanger.
-
-
Heat request K27
: As soon as a heat demand exists in the system, the output K27
will be activated.
-
Heating circuit pump HC1 /HC2
: The relay is used for actuating the heating cir-
cuit pump Q2/Q6.
-
DHW controlling element Q3
: Depending on the hydraulics a connected DHW
charging pump or diverting valve.
Programming
64
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10