POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
SECTION 5
PARAMOUNT
PAGE 21
Display on room control module RRG
Program
No.
BUM parameter final
user level
Function
Basic Setting
(set at factory)
New
Settings *)
700
701
702
703/706
709/712
710/707
710/713
705/708
711/714
715
716
717
Stoer1
StrPn1
StrDial
Stoer2/Stoer3
Stoer4/Stoer5
StrPn2/StrPn3
StrPn4/StrPn5
StrDia2/StrDia3
StrDia4.StrDia5
Stoer_ akt
StrPn_akt
StrDia_akt
1
st
history value for fault code counter
1
st
history value for fault phase
1
st
history value for SE diagnostic code b0
2
nd
/3
rd
/4
th
and 5
th
history value for
fault code counter
2
nd
/34d/4
th
and 5
th
history value for
fault phase
2
nd
/3
rd
/4
th
and 5
th
history value for SW
diagnostic code b0
Current value of fault code counter
Current value of fault phase
Current value of internal SW diagnostic code b0
Display
4)
Display
4)
Display
4)
Display
4)
Display
4)
Display
4)
Display
4)
Display
4)
Display
4)
718
719
720
721
722
723
724
725
755
BetrStd
BetrStdHz
BetrStdBw
BetrStdZone
InbetrSetz
Pmittel
MmiStatus
OT_SwVersLMU
IonStrom
Burner operating time
Heating mode operating time
Hot-water mode operating time
Zone operating time
Start-up counter
Average boiler output
Current summer/winter setting for boiler module
Parameter level
Display of actual ionisation current value
Display (h)
Display (h)
Display (h)
Display (h)
Display (h)
Display (kW)
Display
Display
Display
Other parameters displayed are not relevant for operation of PARAMOUNT!
*) Note : Any new settings to be recorded in manual
1)
These parameters should be altered to suit the specific heating system for optimum comfort and performance.
2)
These parameters should be adjusted only when absolutely necessary
3)
These parameters should never be adjusted
4)
For a list of the internal software diagnosis codes, see RRG manual of the Service Module for a selection of the fault codes see table 6
5)
Parameters only valid if the boiler is equipped with a PWM pump (modulating pump) (Not Potterton supply)
The PARAMOUNT boilers are factory-preset to a single step pump (Parameter 561.0 OFF).
EXPLANATIONS ON ADJUSTMENT TABLE FOR
HEATING ENGINEERS
Explanations of heating engineer level:
The
PARAMOUNT boiler is factory-set for operation and
requires no changes as a rule.
However, a few parameters (see
1
) in the adjustment
table for heating engineer serve for adaptation to the
specific heating system and should be altered to suit
the specific heating system for optimum comfort and
performance.
Note
: The parameters marked with
2
) should only be
readjusted in exceptional cases
when absolutely
necessary.
Explanations on Table 6: A room control module
RRG or service module RRG (optional extra) is
required for adjusting the parameters.
505 (TkSnorm) (modulating pump only):
NOT
REQUIRED U.K.
510 (TuebBw) Boiler temperature setting increase
for hot water charging:
This ensures efficient hot-
water charging. The boiler temperature setting is
increased when hot water is required.
Increase
Quicker charging time; greater overshoot.
Reduction
: Slower charging time; less overshoot.
514 (TuebVor) Boiler temperature setting
increase for VT heating circuit:
Increasing the flow
temperature achieves a constant Variable flow
temperature.
Increasing
: Variable flow temperature
undershoot is avoided.
Lowering
: Variable flow
temperature undershoot possible.
516 (THK) Summer/Winter – Changeover Temp:
The automatic S/W changeover is a function with a
long-term effect which switches off the heating during
the summer when the outdoor temperature is
higher
than the S/W changeover temperature, and switches
it back on only when the outdoor temperature is
below
the value set here for a longer period of time.
S/W changeover via 2 methods:
- By pressing button on heating circuit module HKM
(Fig 7)
- With automatic S/W changeover via outdoor
temperature.
When operated with the room control module RRG,
this module takes over automatic S/W changeover
for the appropriate heating circuits (See RRG
Manual).
When operated with the heating circuit module HKM
and other EUROCONTROL controllers, the
automatic S/W changeover feature (program
No. 516) is effective.