With solar integration
(5093)
This function sets whether the DHW storage tank should be filled.
Pump speed limitations
(5101, 5102)
Setting of the minimum and maximum speed of the storage tank charging pump
in percent.
Speed Xp
(5103)
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to a higher actuation of the charging pump with equal control difference.
Speed Tn
(5104)
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
Speed Tv
(5105)
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
Transfer strategy
(5130)
The transfer is always allowed or to the set DHW release times.
Interm circ boost recharging
(5139)
Setpoint boost for charging setpoint on charging sensor B36 with recharging.
Intermediate circuit boost
(5140)
Setpoint boost for charging setpoint on charging sensor B36 with full charging.
Excess interm circ temp max
(5141)
With this parameter the end criterion of a full charging during control is specified
on the charging sensor B36. If the contents of the layer storage is charge to the
bottom, the temperature increases on the charging sensor
Flow setp compensation de-
lay
(5142)
The filter time for the setpoint lead is set here.
Flow setp compensation Xp
(5143)
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to higher actuation of the charging pump with equal control difference.
Flow setp compensation Tn
(5144)
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
Flow setp compensation Tv
(5145)
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
Full charging with B36
(5146)
Here it can be set whether the end of the full charging is detected via the temper-
ature on the charging sensor B36.
-
No
: the end of the full charging is detected via the temperature on the upper
and lower storage sensor B3 and B31.
-
Yes
: the end of the full charging is detected via the temperature on the upper
storage sensor B3.
Programming
7308272-03 03.14
Paramount three 30-115 kW
105
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...