8.28 Burner control
Prepurge time
(9500)
Pre-venting time.
Note
: This parameter must only be changed by a heating specialist!
Nominal output prepurging
(9504)
Nominal output fan speed during preventing.
Nominal output ignition load
(9512)
Nominal output fan speed during ignition.
Nominal output Partial load
(9524)
Nominal output fan speed under boiler in LF.
Note:
If you change this value, please note that prog. no. 2452 is always set high-
er!
Nominal output Full load
(9529)
Nominal output fan speed under boiler in HF
Postpurge time
(9540)
After-venting time.
Note
: This parameter must only be changed by a heating specialist!
Fan output/speed slope
(9626)
Fan output/speed Y-section
(9627)
With this parameter the rotational speed of the fan can be adjusted (e.g. for com-
plex exhaust systems or the conversion of gas condensing boilers for operating
with liquid gas.
- Prog. no. 9626 equates to the incline of the fan characteristic curve
- Prog. no. 9627 equates to the shift of the fan characteristic curve in Y-direction
8.29 Info Option
Display of different information values which depend on the current operation
state. Furthermore, informations about the different states are displayed (see sec-
tion
State
).
Programming
124
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...