3.4 Sensor value tables
Tab. 3: Resistance values for outside temperature sensor ATF
Temperature [°C]
Resistance [Ω]
-20
8194
-15
6256
-10
4825
-5
3758
0
2954
5
2342
10
1872
15
1508
20
1224
25
1000
30
823
Tab. 4: Resistance values for flow sensor KVS, drinking water sensor TWF, return
sensor KRV, sensor B4
Temperature [°C]
Resistance [Ω]
0
32555
5
25339
10
19873
15
15699
20
12488
25
10000
30
8059
35
6535
40
5330
45
4372
50
3605
55
2989
60
2490
65
2084
70
1753
75
1481
80
1256
85
1070
90
915
95
786
100
677
Technical Data Paramount Three 30-115
7308272-03 03.14
Paramount three 30-115 kW
17