4.
xxxxxxxxxxxxxx
Select the operation mode
automatic operation
with the operation mode but-
ton on the
Auto
(top right of ISR Plus).
5.
Set the required nominal room temperature on the rotating knob of the control
unit
6.3 Temperatures for heating
and drinking water
The information in the section
Programming
for setting the temperatures for heat-
ing and drinking water.
For DHW heating a setting between 50 and 60°C is recommended.
Note:
The times for DHW will be set in time programme 4/ TWW.
For reasons of
comfort, the start of DHW heating should be approximately 1 hour before start of
heating!
6.4 Individual time programme
The gas boiler can be commissioned having its standard time values.
For setting e.g. an individual time programme, please observe section
Time pro-
gram
in
Programming
.
6.5 Programming of necessary
parameters
Normaly, the parameters of the control do not need to be modified (Application
example). Only date/time and possibly time programmes need to be set.
Note:
Setting of the parameters is described in the section
programming
.
6.6 Emergency operation
(Manual operation)
6.6.1 Set emergency operation
• Press OK button
• Select menu point maintenance/service
• Set function manual operation (prog. no. 7140) to "ON"
Heating circuit pumps have been switched on and mixer is set to manual opra-
tion
6.6.2 Adjusting setpoint manual control
Using the operation mode "manual operation" you can choose a nominal tempera-
ture value for it:
Commissioning
40
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...