Function
Prog.
no.
Level
1)
Standard value
Delayed heat request
746
E
0 s
Room influence
750
C
- - - %
Room temp limitation
760
E
0.5°C
Boost heating
770
E
--- °C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
780
E
Down to reduced set-
point
Optimum start control max
790
E
0 min
Optimum stop control max
791
E
0 min
Reduced setp increase start
800
E
--- °C
Reduced setp increase end
801
E
- 15°C
Overtemp prot pump circuit
Off | On
820
E
Off
Mixing valve boost
830
E
5°C
Actuator running time
834
E
120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
850
E
Off
Floor curing setp manually
851
E
25°C
Floor curing setp current
855
E
--- °C
Floor curing day current
856
E
0
Excess heat draw
Off | Heating mode | Always
861
E
Heating mode
With prim contr/system pump
No | Yes
872
E
yes
Pump speed reduction
Operating level | Characteristic
880
E
Characteristic
Pump speed min
882
C
30 %
Pump speed max
883
C
80 %
Curve readj at 50% speed
888
E
10 %
Flow setp readj speed ctrl
No | Yes
890
E
No
Operating level changeover
Frost protection | Reduced | Comfort
898
E
Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
900
E
Protection
Heating circuit 2
Parameter only visible if heating circuit 2 is installed.
Comfort setpoint
1010
Eu
20.0°C
Reduced setpoint
1012
Eu
18.0°C
Frost protection setpoint
1014
Eu
10.0°C
Heating curve slope
1020
Eu
1.50
Heating curve displacement
1021
E
0.0 °C
Heating curve adaption
Off | On
1026
E
Off
Programming
7308272-03 03.14
Paramount three 30-115 kW
55
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...