Function
Prog.
no.
Level
1)
Standard value
Temp differential max
2316
C
---
Temp differential nominal
2317
C
15°C
Pump modulation
None | Demand | Boiler setpoint |Temp differential nominal | Burner
output
2320
E
Demand
Pump speed min
2322
E
10%
Pump speed max
2323
E
100%
Output nominal
2330
E
Paramount Three 30: 28
kW
Paramount Three 40: 38
kW
Paramount Three 60: 50
kW
Paramount Three 80: 70
kW
Paramount Three 95: 90
kW
Paramount Three 115:
110 kW
Output basic stage
2331
E
Paramount Three 30: 6
kW
Paramount Three 40: 9
kW
Paramount Three 60: 12
kW
Paramount Three 80: 17
kW
Paramount Three 95: 20
kW
Paramount Three 115: 25
kW
Output at pump speed min
2334
E
0%
Output at pump speed max
2335
E
100%
Max fan output heating operation
2441
E
Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Programming
60
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...