Function
Prog.
no.
Level
1)
Standard value
Max fan output heating full charging
2442
E
Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Fan output DHW max.
2444
E
Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Fan shutdown heating mode
Off | On
2445
E
Off
Fan shutdown delay
2446
E
3 s
Controller delay
Off | Heating mode only | DHW mode only | Heating and DHW mode
2450
E
Heating mode only
Fan output controller delay
2452
E
Paramount Three 30: 10,0
kW
*)
Paramount Three 40: 14,0
kW
*)
Paramount Three 60: 21
kW
*)
Paramount Three 80: 29
kW
*)
Paramount Three 95: 36
kW
*)
Paramount Three 115: 40
kW
*)
Controller delay duration
2453
E
40 s
Switching diff on HCs
2454
E
4°C
Switching diff off min HCs
2455
E
5°C
Switching diff off max HCs
2456
E
10 °C
Switching diff on DHW
2460
E
5°C
Switching diff off min DHW
2461
E
6°C
Switching diff off max DHW
2462
E
8°C
Delay heat request special op
2470
E
0 s
Programming
7308272-03 03.14
Paramount three 30-115 kW
61
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...