Function
Prog.
no.
Level
1)
Standard value
Antifreeze
None | Ethylene glycol | Propylene glycol | Ethyl and propyl glycol
3880
E
Propylene glycol
Antifreeze concentration
3881
E
50%
Pump capacity
3884
E
200 l/h
Pulse valency
3887
E
10 l
Solid fuel boiler
Locks other heat sources
Off | On
4102
E
Off
Setpoint min
4110
E
65°C
Temp diff on
4130
E
8°C
Temp diff off
4131
E
4°C
Comparative temp
DHW sensor B3 | DHW sensor B31 | Buffer sensor B4 | Buffer sensor
B41 | Flow temp setpoint | Setpoint min
4133
E
Buffer sensor B41
Pump overrun time
4140
E
20 min
Buffer storage tank
Auto heat gen lock
None | With B4 | With B4 and B42/B41
4720
E
With B4
Auto heat gen lock SD
4721
E
5°C
Temp diff buffer/HC
4722
E
-3°C
Min st tank temp heat mode
4724
E
- - - °C
Charging temp max
4750
E
80°C
Recooling temperature
4755
E
60°C
Recooling DHW/HCs
Off | On
4756
E
Off
Recooling collector
Off | Summer | Always
4757
E
Off
With solar integration
No |Yes
4783
E
Yes
Temp diff on return div
4790
E
8°C
Temp diff off return div
4791
E
4°C
Compar temp return div
With B4 | With B41 | With B42
4795
E
With B4
Optg action return diversion
Temp decrease | Temp increase
4796
E
Temp increase
Full charging
Off | Heating mode | Always
4810
E
Off
Full charging temp min
4811
E
8°C
Full charging sensor
With B4 | with B42/41
4813
E
With B42/41
DHW-storage
Parameter subject to the respective system hydraulics.
Charge push forward time
5011
E
60 min
Flow setpoint boost
5020
E
18°C
Transfer boost
5021
E
10°C
Programming
7308272-03 03.14
Paramount three 30-115 kW
63
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...