Function
Prog.
no.
Level
1)
Standard value
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st. time
day | Full charg 1st time legio. charging
5022
E
Full charging
Switching diff
5024
E
4°C
Charging time limitation
5030
E
120 min
Discharging protection
Off | Always | Automatically
5040
E
Automatic
Charging temp max
5050
E
69°C
Recooling temperature
5055
E
80°C
Recooling collector
Off | Summer | Always
5057
E
Off
El imm heater optg mode
Substitute | Summer | Always
5060
E
Substitute
Electrical immersion heater release
24h/day | DHW release | Time program 4/DHW
5061
E
DHW release
El immersion heater control
External thermostat | DHW sensor
5062
E
DHW sensor
Automatic-Push
Off | On
5070
E
On
Excess heat draw
Off | On
5085
E
On
With buffer storage tank
No | Yes
5090
E
yes
With prim contr/system pump
No | Yes
5092
E
yes
With solar integration
No | Yes
5093
E
yes
Pump speed min
5101
E
0%
Pump speed max
5102
E
100%
Speed Xp
5103
E
35°C
Speed Tn
5104
E
120 s
Speed Tv
5105
E
45 s
Transfer strategy
Always | DHW release
5130
E
Always
Interm circ boost recharging
5139
E
5°C
Intermediate circuit boost
5140
E
2°C
Excess interm circ temp max
5141
E
2°C
Flow setp compensation delay
5142
E
30 s
Flow setp compensation Xp
5143
E
60°C
Flow setp compensation Tn
5144
E
30 s
Flow setp compensation Tv
5145
E
30 s
Full charging with B36
No | Yes
5146
E
no
Min start temp diff Q33
5148
E
-3°C
Excess interm circ temp del
5151
E
30 s
Configuration
Programming
64
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...