Function
Prog.
no.
Level
1)
Standard value
Relay output QX21 module 1
Off | On
9050
C
Relay output QX22 module 1
Off | On
9051
C
Relay output QX23 module 1
Off | On
9052
C
Relay output QX21 module 2
Off | On
9053
C
Relay output QX22 module 2
Off | On
9054
C
Relay output QX23 module 2
Off | On
9055
C
Burner control
Pre-purge time
9500
E
15 s
Nominal output pre-purging
9504
E
Paramount 30: 14,5 kW
*)
Paramount 40: 19,5 kW
*)
Paramount 60: 32,0 kW
*)
Paramount 80: 44,6 kW
*)
Paramount 95: 52,0 kW
*)
Paramount 115: 57,0 kW
*)
Nominal output ignition load
9512
E
Paramount 30: 14,5 kW
*)
Paramount 40: 19,5 kW
*)
Paramount 60: 32,0 kW
Paramount 80: 44,6 kW
*)
Paramount 95: 52,0 kW
*)
Paramount 115: 57,0 kW
*)
Nominal output Partial load
9524
E
Paramount 30: 5,6 kW
*)
Paramount 40: 9,0 kW
*)
Paramount 60: 12,0 kW
Paramount 80: 17,0 kW
*)
Paramount 95: 20,0 kW
*)
Paramount 115: 25,0 kW
*)
Nominal output full load
9529
E
Paramount 30: 28,0 kW
*)
Paramount 40: 38,0 kW
*)
Paramount 60: 50,0 kW
Paramount 80: 7
7
,0 kW
*)
Paramount 95: 80,0 kW
*)
Paramount 115: 110,0
kW
*)
Post-purge time
9540
E
10 s
Fan output/speed increase
9626
E
Paramount 30: 214.3
Paramount 40: 150.0
Paramount 60: 106.6
Paramount 80: 76.1
Paramount 95: 65.0
Paramount 115: 60.0
Programming
7308272-03 03.14
Paramount three 30-115 kW
75
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...