Use as
(40)
-
room device 1/2
: this setting establishes which heating circuit the room unit on
which this setting is made should be used. When selecting
room unit 1
the
room device can be assigned to more heating circuits using prog. no. 42, while
with the selection of
room unit 2
only heating circuit 2 can be controlled.
-
Operator unit
: this setting is provided for the pure operation without room
functions and is not needed in connection with this controller.
-
service unit
: this setting is used, for example, to secure or save control settings.
Room controller 1 assign-
ment
(42)
If setting
Room controller 1
(prog. no. 40) was selected at the room controller, de-
termine the heating circuits to which room controller 1 is assigned under prog.
no. 42.
Operation HC2/HC3/P
(44, 46)
When selecting
room unit 1
or
operator unit
(prog.no. 40), it must be set under
prog. no. 44 or 46, if the heating circuits HC2 and HC3/P have to be operated to-
gether with heating circuit 1 or independent from heating circuit 1 by the opera-
tor unit.
Room temperature Unit 1
(47)
Under prog. no. 47 you can select the assignment of room controller 1 to the
heating circuits.
Heating circuit 1 only
: The room temperature is sent exclusively to heating circuit
1.
For all assigned heating circuits
: The room temperature is sent to the heating cir-
cuits assigned under prog. no. 42.
Occupancy button device 1
(48)
You can select the assignment of the occupancy button under prog. no. 48.
None
: Pressing the presence key has no effect on the heating circuits.
Heating circuit 1 only
: The presence key only affects heating circuit 1.
For all assigned HCs
: The presence key affects the heating circuits assigned under
prog. no. 42.
Readjustment room sensor
(54)
The temperature display of the value, transmitted by the room sensor, can be cor-
rected under programme no. 54.
Software version
(70)
Display of the current software version.
8.7 Radio
Detailed descriptions are in the assembly and setting manual of the room device
RGTF.
Device lists
(130 to 138)
The state of the respective device will be displayed under programme numbers
130 to 138.
Delete all devices
(140)
The radio connections to all devices will be cancelled under programme number
140.
8.8 Time programs
Note:
The time programme 1 and 2 are always assigned to the respective heating
circuits (1 - 3) and only displayed if these heating circuits are present and also
turned on in the menu
Configuration
(prog.-no. 5710 and 5715).
Programming
78
Paramount three 30-115 kW
7308272-03 03.14
Summary of Contents for Paramount 40
Page 1: ...Installation manual Gas condensing boiler Paramount three 30 115 kW ...
Page 23: ...Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 23 ...
Page 25: ...Fig 5 Connection plan Prior to installation 7308272 03 03 14 Paramount three 30 115 kW 25 ...
Page 28: ...4 9 Legend Prior to installation 28 Paramount three 30 115 kW 7308272 03 03 14 ...