11
0011211200
Installation of flue
and air ducts
We guarantee ease and flexibility of installation for a
gas-fired forced draft boiler thanks to the fittings and
fixtures supplied (described below).
The boiler is especially designed for connection to an
exhaust flue / air ducting, with either coaxial, vertical
or horizontal terminal. By means of a splitting kit a
two-pipe system may also be installed.
Exclusively install fittings supplied by the
manufacturer.
...coaxial flue - air duct (concentric)
This type of duct allows to disengage exhaust
gases and to draw combustion air both outside
the building and in case a LAS flue is fitted.
The 90
°
coaxial bend allows to connect the
boiler to a flue-air duct in any direction as it
can rotate by 360
°
. It can moreover be used as
a supplementary bend and be coupled with a
coaxial duct or a 45
°
bend.
(*) The restrictor must be removed in case the flue duct length exceeds
1,5 m.
If the flue outlet is placed outside, the flue-air ducting must protrude at
least 18mm out of the wall to allow alluminium weathering tile to be
fitted and sealed to avoid water leakages.
Ensure a 1 cm downward slope per each metre of duct length.
A 90
°
bend reduces the total duct length by 1 metre.
A 45
°
bend reduces the total duct length by 0.5 metre.
0209_3019
0010171400