L max = 14 m
L max = 15 m
Separated vertical flue terminals installation options
Important: if fitting a single exhaust flue duct, ensure it is adequately
insulated (e.g.: with glass wool) wherever the duct passes through
building walls.
For detailed instructions concerning the installation of fittings refer to
the technical data accompanying the fittings.
Split flue air control adjustment
The adjustment of this control is required to optimise performance and
combustion parameters. The air suction coupling which may be mounted
on the left or right of the flue duct can be rotated to adjust excess air
according to the total length of the flue and intake ducts for the combus-
tion air.
Turn this control clockwise to decrease excess combustion air and anti-
clockwise to increase it.
To improve optimisation a
combustion product analyser
can be used to measure the CO
2
contents of the flue at maxi-
mum heat output, gradually ad-
justing air to obtain the CO
2
reading in the table below, if the
analysis shows a lower value.
To properly install this device,
also refer to the technical data
accompanying the fitting.
0209_3012
0003170200
Figure 7
sx
dx
0010172000
CO2%
(L1+L2) MAX
CONTROL POSITION
G.20
G.30
G.31
0
÷
15
1
15
÷
30
2
6
7
7
—
3