Sirius FS
30
GB/IE
5.4.2 Wired Room Units - QAA75 set up
Using the Room unit itself, enter “Commissioning mode” (see section on user levels) and
select “Operator section” Use the following parameter lines to define the setup of this room
unit:
The following example illustrates applications available using the settings “Defined as”
(operating line 40) together with “Heating circuit assignment” (operating lines 42 to 48).
Existing heating circuits 1 and 2 are controlled centrally from room unit 1 for logistical
reasons. The room temperature sensor in room unit 1 is relevant to heating circuit 1 only
since climatic conditions for heating circuit 2 may differ from heating circuit 1. Room unit 2
allows for separate temperature measurements and individually setting of heating circuit 2.
However, operating the occupancy button of unit 1 will activate all heat circuits.
Example settings:-
QAA75, unit 1
QAA75, unit 2
Operating line 40
Room unit 1
Room unit 1
Operating line 42
Heating circuits 1 and 2
Heating circuit 2
Operating line 44
Independently
Independently
Operating line 46
Independently
Independently
Operating line 48
Commonly
None
Line
Display
Notes
28
40
42
44
46
48
54
Define adjustment confirmation message
Define Unit as “Room Unit 1”
Define Unit as “Room Unit 2”
Define Unit as “Room Unit 3”
Assign device (in line 40) to a heating circuit
Defines whether HC1 operates with HC2
Defines whether HC1 operates with HC3
Defines which HC the occupancy button operates
Room temperature adjustment*
*Engineer” level only.
With, Without
Supports HC1
Supports HC2
Supports HC3
HC1, HC2, HC3
(Together or
independent)
HC1, HC2, HC3, ALL
+/- 3
o
C