Configuration C
33
Important
Pipes subject to technical evaluation 14 08–1289.
Fig.81
Maximum length of the connections
MW
-4
0
0
0
2
8
1
-1
L
L
L
L
5
7
8
6
130 - 150 kW
200 - 250 kW
5
8
L
L
L
L
7
6
Tab.26 Maximum length for configuration C
33
Configuration
Unit
SIRIUS THREE FS
130
SIRIUS THREE FS
150
SIRIUS THREE FS
200
SIRIUS THREE FS
250
mm
Ø 110
Ø 110
Ø 160
Ø 160
5
m
L < 8
L < 8
L < 20
L < 11
6
m
L < 8
L < 8
L < 22
L < 12
7
m
L < 6
L < 6
L < 16
L < 6
8
m
L < 7
L < 7
L < 20
L < 9
Configuration C
53
Important
Pipes subject to technical evaluation 14 08–1289.
Tab.27 Maximum length for configuration C
53
Configuration
Unit
SIRIUS THREE FS
130
SIRIUS THREE FS
150
SIRIUS THREE FS
200
SIRIUS THREE FS
250
mm
Ø 110
Ø 110
Ø 160
Ø 160
9
m
(L1 + L2) max = 20
(L1 max) = 10
(L1 + L2) max = 20
(L1 max) = 10
(L1 + L2) max = 42
(L1 + L2) max = 21
Fig.82
Maximum length of the connections
MW
-3
0
0
0
1
7
3
-0
1
L1
L2
9
7 Installation
66