4. Turn the
button to select Full load.
5. Press the
button to adjust the setting.
6. Confirm the selection by pressing the button.
7. Unscrew:
SIRIUS THREE FS
130
SIRIUS THREE FS
150
the left-hand plug, which corresponds to
the flue gas measurement point connec
tion.
SIRIUS THREE FS
200
SIRIUS THREE FS
250
the plug for the rear nozzle.
8. Connect the flue gas analyser to the measurement point.
Important
Ensure that the opening around the sensor is completely sealed
when taking measurements.
SIRIUS THREE FS 130 and SIRIUS THREE FS 150: Insert the
sensor into the flue gas measurement point to at least 8 cm.
9. Set the boiler's heat input to 100% at full load.
10. Measure the percentage of CO
2
in the flue gases.
11. Compare the values measured with the set point values in the Control
and setting values table.
12. If necessary, adjust the air/gas ratio using the gas flow rate
adjustment screw.
Fig.91
MENU
Pleine charge
303:Fonct ramonage
Puissance brûleur
Régler ?
MW-4000284-FR-01
Fig.92
130 - 150 kW
200 - 250 kW
MW-4000278-2
8 Commissioning
7702639 - v03 - 10072018
75