2. Set the following parameters on the boiler:
Tab.20 Boiler settings in 0–10 V mode
Parameter number
Parameter
Adjustment required
5710
Temps / mode CH1
Off
6020
Function extension module 1
Multifunctional
6046
Function input H2 module 1
Consumer request VK1 10V
6049
Voltage value 1 H2 module 1
6050
Funct value 1 H2 module 1
250
6051
Voltage value 2 H2 module 1
6052
Funct value 2 H2 module 1
800
(1) Default setting
(2) This parameter setting is an example. The value 800 means that, at 10 V, the set point will be 80°C.