7704679.01 (3-08/18)
16
7. PUMP CAPACITY/ HEAD
The hydraulic pump, supplied as an accessory kit from POTTERTON COMMERCIAL, is a modulating pump. The purpose of the
pump is to circulate the water between the boiler and the hydraulic separator.
KEY TO PUMP CHARTS - see chap. "BOILER PUMP"
Q
RATE OF FLOW
H
HEAD
THE PUMP FLOW / HEAD CHARTS CAN BE CONSULTED IN CHAP.
"BOILER PUMP"
.
8. ELECTRICAL CONNECTIONS
This machine is only electrically safe if it is correctly connected to an efficient earth system in compliance with current safety
regulations. Connect the boiler to a 230V single-phase earthed power supply using the supplied three core cable, observing
correct Live-Neutral polarity.
Use a double-pole switch with a contact separation of at least 3 mm.
When replacing the power supply cable, fit a harmonised 3x0,75 mm
2
cable with a maximum diameter of 8 mm. To access the
terminal block, remove the front boiler panel (fixed with two screws at the bottom), turn the control box downwards and access
terminal blocks
M1, M2, M3
, used for the electrical connections, after removing the protective cover. The 3.15 A fast-blowing fuses
are incorporated in the power supply terminal block (to check and/or replace the fuse, pull out the black fuse carrier).
SEE WIRING DIAGRAM IN CHAP.
"ELECTRICAL CONNECTIONS"
Make sure that the overall rated power input of the accessories connected to the appliance is less than 2A. If it is higher, install
a relay between the accessories and the electronic board.
The connections in terminal blocks M1- M3 are high voltage (230 V). Before making connections, make sure the appliance is
disconnected from the power supply. Check the input polarity on terminal block M1: L (LINE) - N (NEUTRAL).
TERMINAL BLOCK M1
(L)
=
Live
(brown)
(N)
=
Neutral
(light blue).
=
Earth
(yellow-green).
(1) (2)
= contact for
Room Thermostat
.
Put back the jumper on terminals 1-2 of boiler terminal block
M1 if the room thermostat is not used or if the Remote Control
is installed.
TERMINAL BLOCK M2
Terminals 1 (back-lighting) - 2 (earth) - 3 (+12V):
connection to the
Remote Control (low voltage) supplied as an accessory.
Terminals 4 - 5 (common):
Outdoor temperature sensor
Terminals 6 - 5 (common):
2nd Auxiliary Sensor (sensors for solar
plant, cascade system, zone system, etc.).
Terminals 7 - 5 (common):
1st Auxiliary Sensor (sensors for solar
plant, cascade system, zone system, etc.).
Terminals 9-10:
storage tank sensor connection.
Terminal 8:
not used.
TERMINAL BLOCK M3
Terminal 1-2
: (230Vac - max 1A) power supply of modulating boiler pump (PWM)
Terminal 2-3
: (max 1A) alimentazione pompa non modulante di caldaia (ON - OFF)
Terminal 4
: not used
Terminal 5-6
: PWM signal of the modulating pump
Terminal 7-8
: not used
Terminal 9 - 10
: Domestic Hot Water tank pump (max 1 Amp)
Terminal 11 - 12
: Heating System pump (device connected downstream of the hydraulic separator - max 1 Amp)
If the appliance is connected to an underfloor system, install a limit thermostat to prevent the circuit from overheating.
Use the relative cable grommets at the bottom of the boiler to thread the cables through to the terminal blocks.
A 250Vac/250Vac relay with a minimum current rating of 16A and able to withstand a starting current of above 100A is
required to connect the external pumps.
1
1
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
10
10
1
1
7
7
6
6
5
5
4
4
3
3
2
2
1
1
2
2
N
N
L
L
8
8
9
9
12
12
11
11
10
10
M2
M2
M1
M1
M3
M3
CG_2230
CG_2230
Summary of Contents for Sirius Three WH-130
Page 1: ...May 2018 Sirius three WH 130 150 kW ...
Page 10: ...7704679 01 3 08 18 10 583 892 600 G 1 1 2 G 1 1 2 G 1 198 100 100 100 102 CR_0775 95 223 24 ...
Page 20: ...7704679 01 3 08 18 20 WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Page 35: ...35 7704679 01 3 08 18 29 DIAGRAMS AGU 2 550 CR_0349 CR_0349 AVS 75 bis ...
Page 36: ...7704679 01 3 08 18 36 CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Page 37: ...37 7704679 01 3 08 18 MODIFIED PARAMETERS Nr VALUE NOTE ...
Page 38: ...7704679 01 3 08 18 38 ...
Page 39: ...39 7704679 01 3 08 18 ...